工艺冷却系统控制说明(共4页).doc
《工艺冷却系统控制说明(共4页).doc》由会员分享,可在线阅读,更多相关《工艺冷却系统控制说明(共4页).doc(4页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、精选优质文档-倾情为你奉上系统控制说明:System control instruction1) 联动起动顺序 The order of start 夏季:Summer冷冻水泵制冷机组工艺冷却水泵工艺设备Chilled water pump-chiller-process cooling water pump-process equipment冬季:Winter冷却水泵冷却塔工艺冷却水泵工艺设备Chilled water pump-chiller-process cooling water pump- -process equipment2) 联动停止顺序The order of close夏
2、季:Summer工艺设备制冷机工艺冷却水泵冷冻水泵process equipment-chiller-process cooling water pump-chilled water pump冬季:Winter工艺设备工艺冷却水泵冷却塔冷却水泵process equipment-process cooling water pump-cooling tower-cooling water pump3) 工艺冷却水板式换热器电动阀门控制 Process cooling water heat exchangers electric valve control每个板式换热器冷源端均设置电动二通调节阀门
3、,并在工艺冷却水出水端设置温度传感器,通过温度传感器控制电动二通阀开度,确保出口温度在设定的范围内。当温度小于设定值时,逐渐关闭电动二通阀;当温度大于设定值时,逐渐开启电动二通阀,温度设定值为26+-1。Each heat exchanger cold source side are set electric valve ,and set a temperature sensor in the process cooling water outlet side, by the temperature sensor to control the electric valve opening an
4、d closing, make sure the outlet temperature is within the set range. when the temperature is lower than the set value, gradually close electric valve ; when the temperature is higher than the set value ,and gradually open the electric valve. the temperature setting is 2614) 冷却塔的温控电动阀门控制 The cooling
5、towers electric valve control在冷却水供水主管上设置温度传感器并在供回水主管之间设置电动二通调节阀门,通过温度传感器控制冷却塔风扇启停和电动二通阀开度。Set the temperature sensor in the cooling water supply main pipeline , and set electric valve between cooling water supply and return main pipeline, by the temperature sensor controls the cooling tower fan star
6、 and stop and the electric valve opening or closing .A、冷却塔风扇控制:当水温度低于12,冷却塔风机自动停止运行,当水温高于23时,冷却塔风机按顺序自动回复运行。A、Cooling tower fan control: When the cooling water supply temperature is below 12 , cooling tower fan automatically stops running, when the water temperature is higher than 23 , cooling tower
7、 fan automatic running.B、电动二通阀控制:当水温降至10时,电动二通阀自动缓慢开启;当水温度达到20时,电动二通阀缓慢关闭。当水温达到22时,电动阀完全关闭。B、Electric two-way valve control:When the temperature dropped to 10 , electric valves automatically open slow; when the water temperature reaches 20 , electric two-way valve slowly closed. When the water tempe
8、rature reaches 22 , the electric valve is fully closed.5) 工艺冷却水压力控制 Process cooling waters pressure control工艺冷却水系统为开式系统,在工艺冷却水供水主管上设置压力传感器,每台工艺冷却水泵均采用变频控制,通过压力传感器将实际值与设定值进行比较,并自动控制水泵变频器的频率,确保水泵出口压力在设定的范围内。每台水泵设置故障报警,备用水泵自动启动。在供回水主管之间设置电动二通调节阀和压差传感器,通过压差传感器将实际值与设定值进行比较,并自动控制电动二通调节阀开度,确保工艺冷却水供回水主管之间压差
9、恒定。Process cooling water system for the open system, set a pressure sensor in the process cooling water main pipe, each process cooling water pumps are used frequency control, the measured values to compare with the set value by the pressure sensor, and automatically control the pump frequency conve
10、rter frequency, make sure the pump outlet pressure within a set range. Set failure alarm each pump, standby pump starts automatically. Set electric two-way valve and a pressure difference sensor between the supply and return main pipeline, by the actual value of pressure difference sensor with the s