外文翻译110KV变电站电气一次系统初步设计.doc
《外文翻译110KV变电站电气一次系统初步设计.doc》由会员分享,可在线阅读,更多相关《外文翻译110KV变电站电气一次系统初步设计.doc(10页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、【精品文档】如有侵权,请联系网站删除,仅供学习与交流外文翻译110KV变电站电气一次系统初步设计.精品文档.Efficient Planning of Substation AutomationSystem CablesThanikesavan Sivanthi and Jan PolandABB Switzerland Ltd, Corporate Research,Segelhofstrasse 1K, 5405, Baden-Dattwil, Aargau, SwitzerlandAbstract The manual selection and assignment of approp
2、riate cables to the interconnections between the devices of a substation automation system is a major cost factor in substation automation system design. This paper discusses about the modeling of the substation automation system cable planning as an integer linear optimization problem to generate a
3、n efficient cable plan for substation automation systems.1 IntroductionCabling between different devices of a substation automation system (SAS) is a major cost factor in the SAS design process. Usually computer aided design software is used to create the design templates of SAS devices and their in
4、terconnections. The design templates are then instantiated in a SAS project and the cables are manually assigned to the connections. The selection and assignment of cables to connections must follow certain engineering rules. This engineering process is usually time consuming and can cause engineeri
5、ng errors, thereby increasing the engineering cost. Apparently, the SAS cable planning is related to the well known bin packing problem. The SAS cable planning can be formulated as an integer linear optimization problem with the cable engineering rules expressed as a set of linear constraints and a
6、cost objective for minimizing the total cable cost. This paper describes the formulation of SAS cable planning problem as an integer linear optimization problem and presents the results for some representative test cases. To the best of the authors knowledge the work is the first of the kind to stud
7、y SAS cable planning. The paper is organized as follows. Section 2 presents an overview of the SAS cable planning process. Section 3 expresses the SAS cable planning problem as an integer linear optimization problem. The results obtained by solving the optimization problem using some solvers is pres
8、ented in Section 4. Section 5 draws some conclusions of this work.2 SAS Cable PlanningThe SAS cable planning begins after the system design phase of a SAS project.The SAS cable planning is at present done manually by computer aided designT. Achterberg and J.C. Beck (Eds.): CPAIOR 2011, LNCS 6697, pp
9、. 210214, 2011.cSpringer-Verlag Berlin Heidelberg 2011Efficient Planning of Substation Automation System Cables 211Fig. 1. Fields, devices and their interconnections(CAD) engineers. The different design templates corresponding to the actual devices of a SAS are instantiated in one or more CAD jobs.
10、Each job consists of one or more sheets and each sheet has fields which are logical groups of devices as shown in Figure 1. Moreover, a field corresponds to a physical assembly interface class e.g. Metering box, Protection cubicle etc. Each device has pins which are the physical interconnection inte
11、rfaces of the device. A valid connection is a unique path between exactly two pins and every connection carries a physical signal. A signal can traverse over one or more connections. Each connection is assigned to exactly one of the conductors of a cable. The type of cables to which the connections
12、are assigned is based on cable engineering rules. The cable engineering rules can be classified into two types, namely the cable rules and the signal rules. The cable rules specify the allowed cable types for a set of connections. It can also specify the number of spare conductors which must be left
13、 free in each instance of the allowed cable types. The signal rules specify restrictions on allocation of connections which carry signals that should not be allocated to the same cable or preferably allocated to the same cable. The current practice is to manually select and assign cables to connecti
14、ons according to the cable engineering rules. This procedure is time consuming and can cause engineering errors thereby increasing the engineering cost. In what follows is the formulation of the SAS system cable planning as an integer linear optimizationproblem with which a more efficient cable plan
15、 for SAS can be generated.3 Integer Linear Program FormulationThe SAS cable planning problem is divided into sub problems where each sub problem considers connections between distinct set of field pairs within a given set of CAD jobs. The rationale behind this decomposition is that the cable plan sh
16、ould consider the physical assembly interface classes and should not mix connections between two different source or destination physical assembly interface classes in one cable. This is ensured by deriving a cable plan for each distinct field pairs. Let C = 1, 2, 3, . . .,N represent the set of all
17、 connections between two field pairs, where N is the total number of connections, and K = 1, 2, 3, . . .,M212 T. Sivanthi and J. Polandrepresent the set of all cable types, where M is the total number of cable types in a sub problem. In a cable instance, there can be one or more connections and we r
18、efer to the connection with lowest index among all connections in the cable instance as the leader and the other connections as the followers. This implies that all connections except the first connection in C can either be a leader or follower. Moreover, based on the signal rules a set of connectio
19、n pairs X can be derived where each (i,i) X represents the connections i andi that must not be assigned to the same cable. Let C be the set of connection pairs (i,i) where i,i C, i i, (i,i) / X. We introduce the following binary variable Xi,i, where (i,i) C, which when true implies that connection i
20、 is a follower of a leaderi. (1)Similarly, based on the cable rules a set of connection cable pairs Y can be derived where each (i, j) Y implies that cable type j is not allowed for connection i.Let K be the set of connection cable pairs (i, j), where i C, j K, (i, j) / Y. We introduce the following
21、 binary variable Yi,j, where (i, j) K , which when true implies that the leader i is assigned to an instance of cable type j. (2)Table 1 illustrates all binary variables corresponding to the example shown in Figure 1 for the case with two cable types K1 and K2. It is assumed that connections C1 and
22、C3 cannot be assigned to the same cable and K1 is not an allowed cable type for connection C3. As mentioned before all connections except the first connection, which must be a leader, can either be a leader or follower. This is ensured by the following constraint. (3)A connection which is a leader i