1、TroubleshootingTroubleshootingIntroductionIntroductionSection 5Section 5This section contains Harmony bridge controller (BRC) trou-bleshooting information. Included is information on moduleerror codes, troubleshooting flowcharts, diagnostic routines,and the module status summary.Error codes provide
2、specific module fault information andappropriate corrective action. Troubleshooting flowcharts pro-vide a quick look at hardware associated problems that mayoccur during module installation and startup. Diagnostic testshelp determine if there is a problem with module componentsor circuitry. They are
3、 useful for testing the module when thesystem is down or there is some other means of controlling theprocess. For example, use the backup module (if redundantmodules are installed) to control the process while testing theprimary module. The module status summary is a 16-bytemodule status record that
4、 provides summary flags for errorconditions, module type, and firmware revision level.Error CodesError CodesBRC module error codes are listed in Table 5-1. The moduledisplays error codes on group A LEDs. Table 5-2 lists statusLED states and other conditions that are indicated byLEDs.Table 5-1. Error
5、 CodesTable 5-1. Error CodesCodeCode1 101020305LEDLED8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 10 0 0 0 0 0 0 10 0 0 0 0 0 1 00 0 0 0 0 0 1 10 0 0 0 0 1 0 1ConditionConditionNVRAM checksum errorAnalog input calibrationI/O module status badConfiguration error(undefined block)Corrective ActionCorrective ActionIni
6、tialize NVRAM. If error recurs call ABBfield service.Check I/O module error.Check module status and I/O modules.Check module status undefined block(modules referenced).WBPEEUI230017B15 - 1Error CodesTable 5-1. Error CodesTable 5-1. Error Codes(continued)CodeCode1 106080A0B0C0DLEDLED8 8 7 7 6 6 5 5 4
7、 4 3 3 2 2 1 10 0 0 0 0 1 1 00 0 0 0 1 0 0 00 0 0 0 1 0 1 00 0 0 0 1 0 1 10 0 0 0 1 1 0 00 0 0 0 1 1 0 1ConditionConditionCorrective ActionCorrective ActionConfiguration error (data typeCheck module status (data type) modules.mismatch)Tripblock activatedSoftware programming errorNVRAM initializedNVR
8、AM opened for writeIntermodule link errorCheck module status.Internal error. If error recurs, call ABB fieldservice.Confirm that NVRAM is initialized; noaction is required.Initialize NVRAM. If error recurs, call ABBfield service.Check the cable connection between pri-mary and secondary BRC modules a
9、t thePBA board.Put position 8 of SW2 in the opposite posi-tion of the primary module SW2 position 8.Check configuration. Correct any faultyvalues. Execute the configuration.0E0F0 0 0 0 1 1 1 00 0 0 0 1 1 1 1Redundancy IDs the samePrimary failed, backup can-not take over, configurationnot current100
10、0 0 1 0 0 0 0111213140 0 0 1 0 0 0 10 0 0 1 0 0 1 00 0 0 1 0 0 1 10 0 0 1 0 1 0 0Check configuration. Correct any faultyPrimary failed, backup can-not take over, data not checkvalues. Execute the configuration.pointedError during write tononvolatile memorySet addresses the same.Backup and primary mo
11、duleaddresses are differentROM checksum errorContact ABB field service.Reformat BRC module.BRC set forINFI-NET/Superloop but in aPlant Loop environmentDuplicate Controlwayaddress detectedHnet failureSet address to unique value in PCU.Check Hnet cabling and connections toPBA board, terminations, and
12、HarmonyI/O blocks. Replace the BRC module ifHnet cabling and connections check out.Repeat configuration download.Check file directory, replace bad file.171D0 0 0 1 0 1 1 10 0 0 1 1 1 0 120210 0 1 0 0 0 0 00 0 1 0 0 0 0 1C program format errorFile system error5 - 2WBPEEUI230017B1Error CodesTable 5-1.
13、 Error CodesTable 5-1. Error Codes(continued)CodeCode1 122232425LEDLED8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 10 0 1 0 0 0 1 00 0 1 0 0 0 1 10 0 1 0 0 1 0 00 0 1 0 0 1 0 1ConditionConditionInvoke C errorUser write violationC program stack overflowConfigureable Logic Interface Check firmware revision level. Ve
14、rify that itFunction Code incompatiblesupports the revision the CLIF was com-piled for.with firmwareUser defined function (UDF)Check configuration. Fix block configura-tion. Fix block reference.block number referenceinvalidUDF function block cannotread programMissing UDF declarationWrong UDF typeMis
15、sing UDF auxiliaryCheck configuration. Fix UDF block file.Corrective ActionCorrective ActionCheck C program and invoke C blocks,correct and rerun.Check C program, correct and rerun.280 0 1 0 1 0 0 0292A2B2C2D2E2F3031323334350 0 1 0 1 0 0 10 0 1 0 1 0 1 000 1 0 1 0 1 10 0 1 0 1 1 0 00 0 1 0 1 1 0 10
16、0 1 0 1 1 1 00 0 1 0 1 1 1 10 0 1 1 0 0 0 00 0 1 1 0 0 0 10 0 1 1 0 0 1 00 0 1 1 0 0 1 10 0 1 1 0 1 0 00 0 1 1 0 1 0 1Not enough memory for UDFRevise configuration.Add function code 190 to configuration.Put correct UDF type in configuration.Put function code 198 in blockconfiguration.Check firmware
17、revision level. Verify that itsupports UDF.Check Basic program, correct and rerun.UDF compiler and firmwareincompatibleBasic program errorPrimary active during failoverReplace primary and/or backup to deter-attemptmine faulty module.Memory or CPU faultAddress or bus errorIllegal instructionInternal
18、error - trace/privi-lege violationInternal error -spurious/unassigned excep-tionInternal error - divide by 0 orcheck instructionInternal error - undefined trap Restart BRC module. If error recurs,replace BRC module.Board level hardware errorContact ABB field service.Reset BRC module. If error recurs
19、,replace BRC module.Replace BRC module. If error recurs, callABB field service.Reset BRC module. If error recurs,replace BRC module.3637380 0 1 1 0 1 1 00 0 1 1 0 1 1 10 0 1 1 1 0 0 0WBPEEUI230017B15 - 3Error CodesTable 5-1. Error CodesTable 5-1. Error Codes(continued)CodeCode1 13F4080C0XX2LEDLED8 8
20、 7 7 6 6 5 5 4 4 3 3 2 2 1 10 0 1 1 1 1 1 10 1 0 0 0 0 0 01 0 0 0 0 0 0 01 1 0 0 0 0 0 0ConditionConditionNormal stopBackup - cold takeover readyBackup - hot takeover readyPrimary - operatingUnknownContact ABB field service.None.Corrective ActionCorrective ActionNOTES:NOTES:1. Code numbers are hexad
21、ecimal digits.2. This symbol represents any LED combination not specifically addressed in this table.Table 5-2. Status LED and Other ConditionsTable 5-2. Status LED and Other ConditionsLEDLEDStatusConditionConditionOffCheck power.Check module seating.Check jumper J4. Remove if installed.If power and
22、 seating are okay, remove the moduleand replace with identically configured module.RedGreenGroup A6/7/8OffPress reset button. If LED remains red, remove themodule and replace with identically configured module.None - normal.Check power.Check module seating.If power and seating are okay, remove the m
23、oduleand replace with identically configured module.RedGroup A7/8OffNone - indicates primary module is in simulationmode.Check power.Check module seating.If power and seating are okay, remove the moduleand replace with identically configured module.RedNone - indicates primary module.Corrective Actio
24、nCorrective Action5 - 4WBPEEUI230017B1FlowchartsTable 5-2. Status LED and Other ConditionsTable 5-2. Status LED and Other Conditions(continued)LEDLEDGroup A8ConditionConditionOffCheck power.Check module seating.If power and seating are okay, remove the moduleand replace with identically configured m
25、odule.RedNone - indicates backup module in redundantconfiguration.Corrective ActionCorrective ActionFlowchartsFlowchartsThe flowcharts in Figures 5-1 and 5-2 provide a quick look athardware related problems that may occur during moduleinstallation and startup. Use the flowcharts to troubleshootprobl