1、Four short words sum up what has lifted most successful individuals above the crowd: a little bit more.-author-date变频器设计使用外文文献翻译变频器设计使用外文文献翻译毕业论文(设计)外文资料翻译题目:变频器设计使用参考-Converter reference design(1) Converter Selection: Selection to determine the frequency converter when the following points: 1) The
2、purpose of a variable frequency; constant pressure to control or constant current control. 2) the load converter types such as leaves or pump volume pumps, with special attention to load the performance curve, the performance curve of the decision of the ways and means. 3) the frequency converter an
3、d load matching Voltage match: a rated voltage converter with a rated voltage line with the load. Current matches: ordinary pump, the rated current inverter and motor rated current match. For special load such as deep-water pumps, and so on need to refer to the electrical performance parameters to d
4、etermine the most current inverter current and Guozainengli. Torque match: in this case constant torque load or slow down when the device may have occurred. 4) the use of high-speed motor drive inverter, because of the high-speed motor, anti-small, high harmonics lead to increased output current val
5、ue increases. So for high-speed motor inverter Selection, its capacity to be slightly larger than the ordinary motor selection. 5) If the frequency converter to a long cable run, this time to take measures to curb the long cable to the impact of capacitive coupling, inadequate efforts to avoid conve
6、rter, so in this case, the drive to enlarge the capacity of a file or the converter Output installed output reactor. 6) For the application of some special occasions, such as high temperatures, high altitude, at this time would cause the down converter capacity, the drive to enlarge the capacity of
7、a block. (2) inverter control schematic design: 1) First confirmation of the installation environment Converter Operating temperature: high-power converter is the internal electronic components, vulnerable to the effects of temperature, product general requirements for 0 55 , but in order to ensure
8、the safe, reliable, the use of room to be taken into account, the best control in 40 below. In the control box, the converter box should generally be installed in the upper and strictly comply with the Manual of installation requirements, absolutely not be allowed to heating elements or components e
9、asily fever close to the converter installed at the bottom. Ambient temperature: the temperature is too high and large temperature changes, within easy converter there is dew, the insulation properties will be greatly reduced, or even short-circuit caused the accident. When necessary, to be added to
10、 the desiccant in the box and heater. In water treatment, generally heavier than water vapor, if the temperature changes, then this problem would be more prominent. Corrosive gases: the use of the environment if the corrosive gas concentrations, will not only lead corrosion of components, printed ci
11、rcuit boards, but it will also accelerate the aging of plastic devices, reducing insulation properties. Vibration and shock: the control cabinet with converter by vibration and mechanical shocks will cause electrical connection is bad. Huaian thermoelectric there such a problem. Apart from raising t
12、he control cabinet at this time of the mechanical strength, vibration and shock away from the source, we must also use seismic rubber pad fixed within and outside the control cabinet, such as electromagnetic switches have a vibration components. Equipment operation after a period of time and should
13、conduct inspections and maintenance. Electromagnetic interference: Inverter at work due to rectification and frequency, produce around a lot of electromagnetic interference, these high-frequency electromagnetic waves in the vicinity of the instrument, apparatus, a certain interference. Therefore, th
14、e cabinet instrumentation and electronic systems, it should be optional metal, shielding the inverter instrument interference. All the components should be reliable grounding, in addition, the electrical components, equipment and instrumentation should use the connectivity between the shielding cont
15、rol cables, and the shield should be grounded. If handled properly electromagnetic interference, often cause the entire system does not work, leading to the control unit failure or damage. 2) Drives and determine the distance between the electrical cables and wiring methods Drives and motor the shor
16、t distance should be as much as possible. This reduces the capacitance of the cable, reducing the emission source of interference. Control cables optional shielded cable, power cable or optional shielding from the cable converter to use all the threads of the electrical shield. Electric cables shoul
17、d be independent of the other cable alignment, the minimum distance of 500 mm. At the same time should avoid the electrical cables and other long-running cable lines, in order to reduce the output voltage inverter rapid changes in the electromagnetic interference. If the control cables and power cab
18、les cross, as far as possible so that they cross the 90-degree angle. Converter and analog signals on the line and back to the main line of separation of alignment, even in the case also in the control cabinet. And the analog signal converter line the best choice of unshielded twisted pair, shielded
19、 power cables selection of the three-core cable (its specifications than ordinary electrical cables in the files) or to comply with the user manual converter. 3) inverter control schematics Main circuit: the role of reactor is to prevent the high-frequency converter harmonic power through the input
20、circuit to return to the grid by the impact of other electronic devices, in accordance with the capacity size converter to decide whether to increase reactor; filter Converter is installed in the output, the output of high-frequency converter to reduce harmonics, when the electrical inverter to the
21、longer distance, we should install filters. Although the frequency converter itself has all kinds of protection, but the lack of protection is not perfect, the main circuit breaker played overload, lack the same protection, selection, in accordance with the capacity to choose the frequency converter
22、. Converter itself can be used to replace thermal overload protection relay. Control loop: the frequency with the frequency manually switch to the failure frequency can be manually cut-operation, not because of output voltage, frequency and frequency-be interlocked. 4) Inverter grounding Inverter co
23、rrect grounding is to improve the system stability, the ability to inhibit an important means of noise. Inverter grounding resistance grounding terminal of the smaller the better, the grounding wire cross-section of not less than 4 mm, the length of not more than 5 m. Inverter should be grounded and
24、 power equipment to the sites separately, not in total. The shield signal converter from one end of the grounding end, the other floating air. Inverter and control of electrical between the same counter. (3) Inverter Control Design Converter should be installed in the control cabinet internal contro