1、Generator and Electrical EquipmentsGeneratorIntroduction Electric generators convert mechanical energy to electrical energy, which is more easily transmitted to remotely located points of application. The first large electric generating systems used direct-current (dc) generators, mainly because dir
2、ect current was better understood than alternating current (ac). However, dc generators are limited to generating power at relatively low voltages, largely due to problems at their commutates. As power networks developed, higher and higher voltages were required to transmit large blocks of power ove
3、r longer and longer distances. Electric transformers can easily change the normally low voltage generated to the high voltages needed for efficient power transmission, and of course, transformers only work on alternating current. Ac generators, or alternators as they are commonly called, are so much
4、 simpler mechanically, so much more efficient, and require so much less maintenance than dc machines that all large generating plants output alternating current today. Although de transmission lines can transport extremely large blocks of power very efficiently over long distances, the power is alwa
5、ys generated as alternating current, transformed to the voltage required, rectified and transmitted as direct current, and then inverted back to alternating current at the point of application.Mechanical Energy The mechanical energy for driving the generator must be derived from a source with enough
6、 reliability and capacity to make it economically feasible to develop and transmit the energy electrically to the point of use. A small water supply running only during exceptionally wet years or located at a great distance from electrical consumers would probably not be suitable. Mechanical energy
7、sources which cannot be moved, such as hydraulic turbines or even wind machines, must have the cost of transporting the energy produced (among other factors) taken into account when overall costs are calculated. Steam-turbine power plants, however, can be located near a coal seam, lumber mill, or a
8、reliable source of cooling water to save on transportation costs. Some mechanical power may be obtained from sources more easily located near the point of utilization. Gas turbines and reciprocating gas or diesel engines fall into this category. Except for standby emergency power generators, even he
9、re it might be more economical to install large units and transmit the power to the point of use. Large power plants will generally have better operating efficiencies than small ones, and it may be desirable to locate a large plant near the center of use and then distribute the power generated outwa
10、rd, assuming the fuel supply is transportable.Each type of mechanical driver has its own peculiarities, and some have a sizable impact on the generator configuration. There are marked differences as to the engine output Speeds available, the speed pulsations possible, the chances of overspeed , etc.
11、Normally, the generator shaft is horizontal and direct-connected to the driver. Sometimes speed-changing gear boxes are installed between a high-speed turbine and a lower speed generator. These allow the turbine to run at its most efficient speed, a speed that may be too high for the generator. Smal
12、l hydraulic turbines usually have their shafts mounted horizontally; large hydraulic machines have their shafts direct-connected and vertically mounted. The generator may include special bearings to carry the thrust imposed by the water flowing through the turbine. Criteria like these for providing
13、mechanical energy impose special designs on the generating machines.Basic Principle and Construction There are two quite distinct forms of modem alternator. While the principle of operation of each is the same, i.e. , the movement of magnetic poles past stationary coils, their constructions are very
14、 different. The reason for this is that each has been designed to match its prime mover, i.e., to suit the mechanical device that is to tap the two principal natural power resources-failing water, on the one hand, and steam, generated by heat from fossil fuels or nuclear fuels, on the other. To matc
15、h the output of the turbo alternators, the water wheel generators must therefore be multi-polar and hence of large diameter and small axialength. There is a limit to the length of a turbo alternator, based largely on the mechanical considerations involved in supporting a large rotor mass between a b
16、earing at each end. At 3 000 or 3 600 r/min (50 or 60 Hz) the rotor must be extremely well balanced and its surface smooth. With the lower speed water powered machine, such precautions can be relaxed with a view to making the larger rotor cheaper to make. The fundamental difference in shape between
17、the rotors of the two types of machine is consequent upon the above considerations, but now a secondary difference is introduced by what could be termed the experience and skill of the designer. It is necessary to produce a sine wave of induced e.m.f. The factors that affect the instantaneous value
18、e of this are the flux density b , the length I of the conductor, and the velocity v (the use of small letters indicating the instantanous values). Thus: = b l v (4.1) A reasonably clear definition of what constitutes a pole can be given by defining a pole pitch rather than a pole per se. A pole pit
19、ch is the distance ( p ) between points where the current flow is a maximum. The number of poles in the machine is then the periphery ( 2r ) divided by p . This definition fits easily into linear motor technology, where the number of poles need be neither even nor an integer. The speed of rotation e
20、xpressed in Table 4.1 as 2 f/n r/s, where n was the number of poles, can always be converted to a linear speed, for the periphery 2 r contains n pole pitches each of length p so that 2r = n p . Hence the rotational speed 2 f/n /r/s translates into a linear speed, v s , such that v s=(2 f / n) (2r)=
21、(2 f / n) (n p)=2pf (4.2) which is simply the common sense statement that a travelling wave moves two pole pitches ( = one wavelength; A ) each cycle of events. (This corresponds to the well known formula v = f for all wave motions. ) Three-phase machine stator shown in Figure 4. l (a). It does not,
22、 as it appears at first sight, have six poles, even though it has six obvious polar projections. These are to be seen as six teeth in a slotted stator with a three-phase distributed winding, except that the distribution has virtually disappeared except insofar as there are three phases. Unless such
23、a diagram makes clear how the two coils in each phase are connected, no one can say whether it has two poles or four. It is worth studying Figure 4.1 carefully, first to appreciate the differences between(b)and (c), hence to see the kind of difficulty that can arise in the mind of the student being
24、confronted with the problem for the first time, and finally to demolish the problem so that it never arises in the future. For the connections shown at (b), both red-phase coils assist each other in driving flux diametrically across the machine. So do both yellow-phase coils and both blue-phase coil