1、Programmable Logic Controllers (PLCS) 1 About Programmable Logic Controllers (PLCs) PLCs (programmable logic controllers) are the control hubs for a wide variety of automated systems and processes. They contain multiple inputs and outputs that use transistors and other circuitry to simulate switches
2、 and relays to control equipment. They are programmable via software interfaced via standard computer interfaces and proprietary languages and network options. Programmable logic controllers I/O channel specifications include total number of points, number of inputs and outputs, ability to expand, a
3、nd maximum number of channels. Number of points is the sum of the inputs and the outputs. PLCs may be specified by any possible combination of these values. Expandable units may be stacked or linked together to increase total control capacity. Maximum number of channels refers to the maximum total n
4、umber of input and output channels in an expanded system. PLC system specifications to consider include scan time, number of instructions, data memory, and program memory. Scan time is the time required by the PLC to check the states of its inputs and outputs. Instructions are standard operations (s
5、uch as math functions) available to PLC software. Data memory is the capacity for data storage. Program memory is the capacity for control software. Available inputs for programmable logic controllers include DC, AC, analog, thermocouple, RTD, frequency or pulse, transistor, and interrupt inputs. Ou
6、tputs for PLCs include DC, AC, relay, analog, frequency or pulse, transistor, and triac. Programming options for PLCs include front panel, hand held, and computer. Programmable logic controllers use a variety of software programming languages for control. These include IEC 61131-3, sequential functi
7、on chart (SFC), function block diagram (FBD), ladder diagram (LD), structured text (ST), instruction list (IL), relay ladder logic (RLL), flow chart, C, and Basic. The IEC 61131-3 programming environment provides support for five languages specified by the global standard: Sequential Function Chart,
8、 Function Block Diagram, Ladder Diagram, Structured Text, and Instruction List. This allows for multi-vendor compatibility and multi-language programming. SFC is a graphical language that provides coordination of program sequences, supporting alternative sequence selections and parallel sequences. F
9、BD uses a broad function library to build complex procedures in a graphical format. Standard math and logic functions may be coordinated with customizable communication and interface functions. LD is a graphic language for discrete control and interlocking logic. It is completely compatible with FBD
10、 for discrete function control. ST is a text language used for complex mathematical procedures and calculations less well suited to graphical languages. IL is a low-level language similar to assembly code. It is used in relatively simple logic instructions. Relay Ladder Logic (RLL), or ladder diagra
11、ms, is the primary programming language for programmable logic controllers (PLCs). Ladder logic programming is a graphical representation of the program designed to look like relay logic. Flow Chart is a graphical language that describes sequential operations in a controller sequence or application.
12、 It is used to build modular, reusable function libraries. C is a high level programming language suited to handle the most complex computation, sequential, and data logging tasks. It is typically developed and debugged on a PC. BASIC is a high level language used to handle mathematical, sequential,
13、 data capturing and interface functions. Programmable logic controllers can also be specified with a number of computer interface options, network specifications and features. PLC power options, mounting options and environmental operating conditions are all also important to consider.2 INTRODUCTION
14、For simple programming the relay model of the PLC is sufficient. As more complex functions are used the more complex VonNeuman model of the PLC must be used. A VonNeuman computer processes one instruction at a time. Most computers operate this way, although they appear to be doing many things at onc
15、e. Consider the computer components shown in Figure 1.Figure 1 Simplified Personal Computer ArchitectureInput is obtained from the keyboard and mouse, output is sent to the screen, and the disk and memory are used for both input and output for storage. (Note: the directions of these arrows are very
16、important to engineers, always pay attention to indicate where information is flowing.) This figure can be redrawn as in Figure 2 to clarify the role of inputs and outputs.Figure 2 An Input-Output Oriented ArchitectureIn this figure the data enters the left side through the inputs. (Note: most engin
17、eering diagrams have inputs on the left and outputs on the right.) It travels through buffering circuits before it enters the CPU. The CPU outputs data through other circuits. Memory and disks are used for storage of data that is not destined for output. If we look at a personal computer as a contro
18、ller, it is controlling the user by outputting stimuli on the screen, and inputting responses from the mouse and the keyboard.A PLC is also a computer controlling a process. When fully integrated into an application the analogies become;inputs - the keyboard is analogous to a proximity switchinput -
19、circuits - the serial input chip is like a 24Vdc input cardcomputer - the 686 CPU is like a PLC CPU unitoutput - circuits - a graphics card is like a triac output cardoutputs - a monitor is like a lightstorage - memory in PLCs is similar to memories in personal computersIt is also possible to implem
20、ent a PLC using a normal Personal Computer, although this is not advisable. In the case of a PLC the inputs and outputs are designed to be more reliable and rugged for harsh production environments.3 OPERATION SEQUENCEAll PLCs have four basic stages of operations that are repeated many times per sec
21、ond. Initially when turned on the first time it will check its own hardware and software for faults. If there are no problems it will copy all the input and copy their values into memory, this is called the input scan. Using only the memory copy of the inputs the ladder logic program will be solved
22、once, this is called the logic scan. While solving the ladder logic the output values are only changed in temporary memory. When the ladder scan is done the outputs will be updated using the temporary values in memory, this is called the output scan. The PLC now restarts the process by starting a se
23、lf check for faults. This process typically repeats 10 to 100 times per second as is shown in Figure 3.Figure 3 PLC Scan CycleSELF TEST - Checks to see if all cards error free, reset watch-dog timer, etc. (A watchdog timer will cause an error, and shut down the PLC if not reset within a short period
24、 of time - this would indicate that the ladder logic is not being scanned normally).INPUT SCAN - Reads input values from the chips in the input cards, and copies their values to memory. This makes the PLC operation faster, and avoids cases where an input changes from the start to the end of the prog