1、-五岳压力表pw206英文手册-第 5 页PW206 digital pressure controller1. New FeaturesThis controller has two-layer structure, top for displaying actual pressure and bottom for set pressure. It has top and bottom limit alarms, two sets alarm,outputing by relay contact point . It can output by constant current and vo
2、ltage,4-20mA or 0-10 V linear output analog data. It also can connect to the PLC and other controllers directly with automatic panel calibration function which makes the calibration much easier like just pressing some keys. This controller also adopts light and electricity insulation, watch dog, sof
3、tware wave filtering these three types anti-interference technology. It ensures the reliability of the system. This controller supplies by switch, so it can work at 120V low voltage conditions.This controller is widely used in the petroleum, chemical fiber, and plastic industry. It can used with the
4、 normal controller for pressure test and control at normal temperature. Based on PW200 series, PW800 series are one new generation of intelligent instruments. Main technical detailsItemDescriptionDisplayTwo-layer structure, top for actual pressure and bottom for set pressureInternal Resolution32000E
5、xternal Resolution0.1 MPa,0.02MPa,0.05MPa data save for more than 40 years after disconnectionPower supply220VAC(120V-250V)Range099.99MPaRelay rating250VAC 5AOperating environment-10-55, 99% RHDimension96X96 X 100mmConfigurable output for pressure420mA, 05V, 010V optional2.Configuration and overall
6、dimensionPV display :LED large nixie tube for display the current pressure. It will display parameters code name while you change the parameters.SV display: LED small nixie tube for display the top limit pressure(AL1). It will display the current parameter which you are revising.Introduction of keyp
7、adCE: zero clearing button.CAL: calibration button (Automatic calibration button).:Shifting button: Move button:Decreasing value button:Increasing value buttonIntroduction of indication lightAL1top limit alarm indication light AL2-lower limit alarm indication lightCALcalibration indication light (th
8、e light will flicker when performs the automatic calibration).3. Wiring diagram on the display backside.1, 2.AL1 relay output normal open2, 3.AL1 relay output normal close4, 5.AL2 relay output normal open5, 6.AL2 relay output normal close7,8 AC supply input9. Sensor signal positive S+ (blue wire)10.
9、 Sensor positive S+ (red wire)11. Sensor signal negative S- (black wire)12. Sensor negative E- (yellow wire)13. Sensor calibration C (green wire)14. Shield15. Output+16. Output-4. Basic operation and operation guide1. starting upAfter wiring work is finish, and then connect the display with supply f
10、or self-check. During the self-check, the PV display will display working position and minimal resolving power. The two front number of SV display will show the actual measurement valve, the back number will show minimal resolving power. The display will go back to working position after self-check
11、automatically. At the working position, the upper PV display will show actual working pressure, the bottom PV display will show up limit alarm set valve.When the display is showing the following figure: it means measurement range is 50 MPa, division valve is 0.02Mpa.PV50.00 SV MPa 5C.22. Change SV s
12、et valve(up limit valve AL1) When the display is at working position, press the shifting button to make SVs last number flicker, then you can change the up limit alarm setting valve by press the move button, increasing valve button, decreasing valve button. Please press shifting button another time