2022年2022年洁净空调系统用户需求描述URS .pdf
《2022年2022年洁净空调系统用户需求描述URS .pdf》由会员分享,可在线阅读,更多相关《2022年2022年洁净空调系统用户需求描述URS .pdf(11页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Specification(URS)for HVAC systems Page 1 of 11 User Requirement Specification(URS)for HVAC Systems 洁净空调系统用户需求描述Project Name项目名称Extension of BWM Facility at BJMC 北京制造中心 BWM 扩建(年产 1800万平米)Project No.项
2、目编号工程-BWM-2010-1-000Plant/Building 工厂/建筑物BJMC-Huai Rou 北京制造中心-怀柔/A 区 4#厂房内Unit 单元HVAC 洁净空调系统Equipment设备AHU11/12#洁净空调系统Document Code文件编号BJMC_MRS_HVAC_AHU11/12_URS_1.0 Revision 1.0 Name Signature Reason Function/Department Date Signature Li Xiao sheng Author Technology Manager Mark Hu Approver Project
3、 Manager Chen Huizhong Approver Construction Manager 名师资料总结-精品资料欢迎下载-名师精心整理-第 1 页,共 11 页 -BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Specification(URS)for HVAC systems Page 2 of 11 Table of Content目录1.Objectives综述.32.Demand Analysis要求分析.33.Pr
4、ocess 工艺过程.33.1Product Characteristics产品特点 .34.Production Strategy生产组织特征 .35.Location 位置.46.Technical Concepts技术要求 .46.1Design Basis设计基础 .46.1.1Outdoor conditions室外气象条件.46.1.2Noise level 噪音等级 .46.1.3Room Performance requirements 房间性能要求.46.1.4Air Change Rates(ACR)换气次数 .66.2General HVAC design require
5、ments洁净空调设计的一般性要求.76.3Specific HVAC design requirements特殊的洁净空调设计要求.86.4Energy recovery能量回收.86.5Supporting Utilities 动力供应 .96.6Controls 控制.96.7Pressure&Zoning Diagram 压力和洁净区域平面图.97.Authorities 政府.98.Health,Safety,Environment(HSE)健康,安全,环境.99.cGMP Requirements cGMP的要求.910.Documentation文件存档 .1011.Exclus
6、ions/Limitations 缺陷/不足.1012.Schedule时间计划 .1013.Project Costs项目费用.1014.Alternatives&Open Items to above topics遗留条目.1015.Abbreviations 缩写.1016.Attachment 附件.11名师资料总结-精品资料欢迎下载-名师精心整理-第 2 页,共 11 页 -BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Speci
7、fication(URS)for HVAC systems Page 3 of 11 Revision History版本修订历史Reasons for changes compared to previous version 版本修订的原因Revision No.版本号Date 日期Name of Author 作者姓名Description of Changes 版本升级原因1.Objectives综述This URS covers the general requirements for the HVAC systems within the Project Extension of R
8、SM Facility of Beijing Austar PharmMed Consumable Packaging Ltd.,本 URS 涵盖了朗活医药耗材(北京)有限公司的年产1800 万平米扩建工程的对洁净空调系统的一般性要求。2.Demand Analysis要求分析1、整个生产区域均为万级;温度18-26,湿度 45%-65%。2、辅助区域利用原有BWM2 的物流通道和供料间,设施按照使用量进行扩充;利用 PCM2 的人流通道和设施。3、挤出间设备发热量非常大,需要特殊考虑降温措施以实现232。相对粉尘偏大。3.Process 工艺过程3.1 Product Characteris
9、tics产品特点1、挤出间设备发热量非常大,需要特殊考虑降温措施以实现232。相对粉尘偏大。2、吹膜过程对温度波动较为敏感,期望温度精度控制在2以内,但温度变化曲线不大于 1/h。3、膜产品易产生静电,室内相对湿度应保持在45-65%之间。4、该产品属于大输液包材,表面菌落、游离异物等应符合13 号令要求。4.Production Strategy生产组织特征The HVAC systems will operate continuously(7 days/24 hours).In non operation hours the air volume will be reduced by ma
10、intaining the room pressure.名师资料总结-精品资料欢迎下载-名师精心整理-第 3 页,共 11 页 -BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Specification(URS)for HVAC systems Page 4 of 11 本项目通常会连续运行;个别情况下会停机检修、待产。通常待产时间超过4小时允许停止空调运行;但在停机复产前必须提前2 小时开启空调进行预净化。挤出间常规操作人员1人;收卷间常
11、规操作人员4 人。5.Location位置The location of the HVAC facilities is basically on the technical floor and installed on platforms or roofs.1、该机组会安装到技术夹层中;2、怀柔春秋风沙相对较大;3、现场有顶标高6 米的网架梁,设计单位面积承载200kg;屋顶最低点高度8.5米。6.Technical Concepts技术要求6.1 Design Basis设计基础6.1.1 Outdoor conditions室外气象条件Average High Dry Bulb tempe
12、rature 33 C Summer Highest Dry Bulb temperature 38.4 C Relative Humidity-High 80%Average Low Dry Bulb temperature-2.4 C Winter Lowest DB temperature-18.0 C Relative Humidity-Low 65%依据北京市怀柔区常年气象指数。6.1.2 Noise level 噪音等级Requirements GMP Relevance Max.site boundary noise level is 85 dBA Noise level due
13、 only to the HVAC plant Manufacturing areas 60 dB(A)NO 6.1.3 Room Performance requirements房间性能要求6.1.3.1 Cleanliness Zones 洁净等级要求名师资料总结-精品资料欢迎下载-名师精心整理-第 4 页,共 11 页 -BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Specification(URS)for HVAC systems
14、 Page 5 of 11 Room房间Cleanliness Zones 洁净等级要求GMP Relevance 挤出间 room1 10000级Yes 收卷间 room2 10000级Yes 分切间 room3 10000级Yes 6.1.3.2 Pressurization concept气流压力等级组织形式Room 房间Pressure differential 压差GMP RelevanceRoom1 to Outside房间 1 对室外5-20Pa Yes Room1 to Room 2房间 1 对房间 2-50PaYes Room2 to Room 3房间 2 对房间 3 2Pa
15、以内Yes Room3 to Outside房间 3 对室外5-20Pa Yes 6.1.3.3 Temperature and relative Humidity Concept温度和相对湿度的要求Room 房间Requirements要求GMP Relevance ROOM1 Temperature according the Policy:23C 3 C Relative Humidity according the Policy:55%10%YES ROOM2 Temperature according the Policy:22C 4 C Relative Humidity acco
16、rding the Policy:55%10%YES ROOM3 Temperature according the Policy:22C 4 C Relative Humidity according the Policy:55%10%YES 6.1.3.4 Filter concept过滤器要求Requirements GMP Relevance Generally filters shall be selected according to EN 779&EN 1822 norms.过滤器选择应符合EN779和 EN1822的要求YES 名师资料总结-精品资料欢迎下载-名师精心整理-第
17、5 页,共 11 页 -BJMC Beijing Austar PharmMed Consumable Packaging BJMC_BWM_HVAC_AHU11/12/12_URS_1.0 User Requirement Specification(URS)for HVAC systems Page 6 of 11 Requirements GMP Relevance The frames for the HEPA filter housings shall be testable for tightness by a test groove.高效过滤器安装后应对安装框架的密封性进行试验,
18、以确保密封良好YES 高效静压箱(或高效风口)要求有检测孔,以便检测滤效、压差等Yes 通常空调机箱内选配G3、F7;末端高效选配H13(AAF、苏净等知名品牌)。6.1.4 Air Change Rates(ACR)换气次数The required ACRs will be determined based on required cooling load,heating load,relative humidity,pressurization,recovery times,particulate control etc.要求的换气次数取决于冷负荷,热负荷,相对湿度,压力等级分布,自净时间