1、XJK-LG5 Refrigerated Air Dryer Controller User ManualThanks for your choose XJK-LG5 refrigerated air dryer controller, please read the manual before use. And operation should be complied with the manual.I Main Functionl Local/Remote control the work of compressor and drain valve automaticallyl Link
2、signal control the work of controllerl Detect temp. of each part of systeml LCD display running/alarm information and parameter value l Output alarm signall Communication with PC (RS485)l Output a start signal for subordinate after compressor work II Technical Datal Rating voltage: AC220V(+15%,-20%)
3、.l Analogy input: 5 channels of temperature l 6 channels of relay output (include energize, Y, , drain, alarm, subordinate machine start)If the voltage of contact is AC 220V, then the sensitive load current of contact is 0.8A, the resistance current of contact is 2A.l Digital input signal: 4 buttons
4、 (include =, , , run/stop), alarm signal (N.C), link start signal.l Display: 12832 lattice LCD screen, 2.99 (76mm) wide by 0.98 (25mm) tall.l Shell size: 218150115. Its panel-mount, the recommended panel cutout for the controller is 8.27 wide (210mm) by 5.51 tall (140mm). III Display1. LCD2-4. light
5、-emitting diode alarm5-8. button9. light-emitting diode compressor work10. light-emitting diode inlet gas temperature too high.11. light-emitting diode dew point temperature too high12. light-emitting diode drain valve workFollowing table lists function of each button.NO.Button Definition 1=1.Press
6、and hold over 2 seconds in standby mode, enters into program mode2. Choose next parameter in program mode.3. Confirm input password.4. Confirm new password after modify.21. Add value of current parameter in program mode2. Input password (add)3. Read the other temperature detect value31. Minus value
7、of current parameter in program mode2. Input password (minus)3. Release output alarm signal, but LCD also displays alarm information4RUN/STOP1. ON/OFF controller2. Exit program mode, and save modified values5=+Enter into junior password input screen in program mode6=+ Enter into senior password inpu
8、t screen in program modeIV Explanation for parametersTo successfully program this controller, you must first understand how it works and what you are programming into it. Model LG5 controller has 3 class of parameter, class 1 for normal use, class 2 for compensation and other important parameter, cl
9、ass 3 for upper limit of total work time.Table 1 parameter list of class 1Parameter Definition Set rangeInlet gasHigh temp. alarm of inlet gas2090Dew point If detect dew point preset of dew point, temperature of dew point will not take part in control.130Note 1: work procedure of drain valve, please
10、 see section VI.Note 2: if preset value of return-dew point preset value of dew point, shield dew point take part in control logic.Table 2 parameter list of class 2Parameter Definition Set rangeTemp. com.t1Compensation of inlet gas temp.-9 - 9t2Compensation of dew point -9 - 9t3Compensation of outle
11、t gas temp.-9 - 9t4Compensation of condensation temp.-9 - 9t5Compensation of evaporation temp.-9 - 9T-switchY- switch time when compressor start 1 99sAddressCommunication address1-30Delay timeDelay time to start subordinate machine after compressor work1-99 mLock time Delay time of restart compresso
12、r after turn off compressor1-999 sUp delayDelay time before start controller when receive link start signal0-99sNote 3: after lock time, press RUN/STOP, output relay of Energize and Y are closed, compressor start to work, and light-emitting diode 9 (compressor) light. After time of preset of T-switc
13、h, output relay of Y is open and output relay of is closed, Y/ connection finished.Note 4: preset value of address should be equal to the address set in host monitor software.Note 5: compressor stop work or controller is energized, count down the preset value of lock time, enter into lock protect st
14、ate, controller not answer any order. Note 6: after receive the link start signal, controller no start to work immediately, it will delay the time of preset of up delay. Table 3 parameter list of class 3Parameter Definition Set rangeTotalUpper limit time of total work time 0-9999 hNew codeSenior cod
15、e0-9999Note 7: if the preset of total is 0 means that there is no upper limit for total work time. If the preset is nonzero, and the total work time is up to the preset (LCD is bright, but display nothing, and light-emitting diode 4 twinkles), the controller doesnt answer any order when restart it.
16、Modify the preset value of total can make the controller work again.Note 8: the new password should press = button to make it effective. And next time, input the new password.V Program After energizing, the controller enters into lock protect state, as figure 10. After lock time, enters to standby s
17、tate, as figure 8. 1) Program class 1 parameter Press = button in standby mode to enter into program mode. And the LCD will display as the figure 1. Current parameter value is displayed in black background. Press / button to add or minus the preset value. E.g. if the preset value of inlet gas displa
18、ys in black background, means current parameter is inlet gas, press / button to modify the value. Press button to add, the upper limit of inlet gas is 120. Press button to minus, the lower limit of inlet gas is -19. Press / button continually, the value add or minus quickly.Figure 1Press = button to
19、 choose the next parameter. Show as the figure 2.Figure 2Note 9: if the preset of dew point difference the preset of dew point, means the dew point is only used to display, and not take part in control. When you finish program and wish to exit program mode, press run/stop button. Or if there isnt an