制冷技术(英文版).doc
《制冷技术(英文版).doc》由会员分享,可在线阅读,更多相关《制冷技术(英文版).doc(19页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、Chapter 5. Vapor and Gas Refrigeration Cycles 5-1) Mechanical Powered Vapor Compression Refrigeration Cycle 5-2) Heat Powered Vapor Compression Refrigeration CycleVapor Absorption Refrigeration 5-3) Heat Powered vapor Compression Refrigeration CycleVapor Adsorption Refrigeration 5-4) Heat Powered va
2、por Compression Refrigeration Cycle Vapor Jet Refrigeration 5-5) Refrigeration Cycle by Gas Compression and Adiabatic Expansion 5-1) Mechanical Powered Vapor Compression Refrigeration Cycle(1) Introduction of mechanical powered vapor compression refrigeration cycle Hot heat reservoirHeat sink Refrig
3、eration cycleCondenser Evaporator Compressor Metering DeviceFluid to be cooled(Refrigeration load) Cooling fluidHeat source Cold heat reservoirFig.2-1, The Model for Analysis of Refrigeration CycleThe mechanical vapor compression refrigeration is the most common refrigeration cycle. Its advantages,
4、in comparison with other types of refrigeration systems, include the compact of the system; high coefficient of performance (COP); being reliable, safe and flexible in operation; relatively simple in maintenance; and low initial costs. (2) Basic vapor compression refrigeration cycle举个例子Here take the
5、 Refrigerant R134a as an example to show how to calculate the cycles cooling capacity and COP by assuming that the refrigerant leaves the evaporator at the temperature of -20C and it is condensed at 40C. For the case of evaporating temperature and condensing temperature, the thermal properties of R1
6、34a can be found from the diagram or table of the refrigerant R134a as below:Evaporating pressure Condensing pressure The specific enthalpies of R134a at these states are: (It is an isentropic process from point1 to point2.) Fig.5-1, Schematic and a log p-h diagrams for the basic vapor compression c
7、ycleThe process 1-2 is a reversible, adiabatic (isentropic) compression (5-1)The process 2-3 is an isobaric heat rejection process (5-2)The process 3-4 is an irreversible throttling process, The process 4-1 is an isobaric constant pressure heat admission process (5-3)The coefficient of performance o
8、f the cycle can be calculated as: (5-4)If the mass flow rate of the refrigerant R134a through this cycle is m=0.1kg/s, then the refrigeration capacity, the condensing load and the work of compression can be gotten as: 5-2) Heat Operated Vapor Compression Refrigeration Cycle (1)Vapor Absorption Refri
9、geration (还是蒸汽压缩式制冷,降温方法一样(p.53),区别只在于压缩方式)有热能可以利用的场合There is abundant thermal energy appeared in different forms in the world, such as solar thermal, geothermal, various wasted heats and biomass energy etc. These energies can be used to drive refrigeration and air-conditioning systems.3种热驱动的蒸汽压缩式制冷
10、There are three kinds of vapor compression refrigeration cycles that can be driven by thermal energy. They are: 1,the absorption refrigeration cycle, 2,the adsorption refrigeration cycle and 3,vapor jet refrigeration cycle. These cycles share similar technologies that are used in the vapor compressi
11、on refrigeration cycle, i.e., throttling evaporating and condensing. but they are driven by thermal energy. These refrigeration cycles will discussed in this chapter. (1) Principles of absorption refrigerationFig.5-2, essential components of the vapor absorption cycleThe mechanical compressor is rep
12、laced by a thermal compressor which consists of absorber, solution pump, generator (or boiler) and liquid valve. This group of components sucks vapor from the evaporator, and delivers high pressure vapor to the condenser, just as the mechanical compressor does but the vapor is actually absorbed by a
13、 liquid absorbent . Aqua ammonia and aqua lithium bromide solutions are commonly used in vapor absorption refrigeration systems.氨水吸收的蒸汽压缩式制冷系统The absorption of ammonia by water is an exothermic process. The strong solution formed in the absorber is pumped to the generator at higher pressure. In the
14、generator, the strong solution is boiled by heating, and the vapor given off is rectified to nearly pure ammonia and delivered to the condenser. There is a heat exchanger interposed between the generator and absorber. The hot weak solution from the generator transfers the heat to the strong solution
15、 from the absorber. To maintain the difference in pressures between the generator and absorber, a valve is installed in the pipe 4, 5The refrigerants and absorbent in H2O-LiBr system and NH3H2O systemAbsorption cyclerefrigerantAbsorbentH2OLiBr systemH2OLiBr solutionNH3H2O systemNH3H2O溴化锂水吸收的蒸汽压缩式制冷系
16、统In lithium bromide-water absorption refrigeration systems, water is the refrigerant and lithium bromide is the absorbent. This explains that the lithium bromide absorption system is strictly limited to evaporation temperatures above 0C; and the ammonia absorption system is mainly used for low tempe
17、ratures below 0C. Water as a solvent in ammonia absorption system is present in the vapor so rectification is required to remove it, whereas LiBr (a hygroscopic salt) is almost non-volatile at the operating conditions so rectification is not necessary (2) Composition of mixtures Calculation of absor
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 制冷 技术 英文
限制150内