1、 HAT833(HAT833/HAT833S)THREE POWER ATS CONTROLLER USER MANUAL All rights reserved.No part of this publication may be reproduced in any material form(including photocopying or storing in any medium by electronic means or other)without the written permission of the copyright holder.Applications for th
2、e copyright holders written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above.Any reference to trademarked product names used within this publication is owned by their respective companies.SmartGen Technology reserves the right to ch
3、ange the contents of this document without prior notice.Table 1-Software Version Date Version Note 2018-10-16 1.0 Original release.2018-12-13 1.1 Modified controller front panel picture.2020-02-13 1.2 Modified typical application diagram,added mutual lock for each power close.2020-10-10 1.3 Modified
4、 the Chinese interface display of the controller.2021-04-20 1.4 1.Add the HAT833S function descriptions;2.Changed“Mains-Gen-Mains”to“Mains-Gen-Gen”in“Performance and characteristics”;3.Modified the manual font and the format of header and footer.CONTENT 1 OVERVIEW.5 2 NAMING CONVENTION AND MODEL COM
5、PARISON.6 2.1 NAMING CONVENTION.6 2.2 MODEL COMPARISON.6 3 PERFORMANCE AND CHARACTERISTICS.7 4 SPECIFICATION.8 5 MEASURE AND DISPLAY DATA.9 6 OPERATION.10 6.1 INDICATORS.10 6.2 KEY FUNCTION DESCRIPTION.11 7 LCD DISPLAY.12 7.1 MAIN SCREEN.12 7.2 STATUS DESCRIPTION.13 7.3 MAIN MENU.18 8 START/STOP OPE
6、RATION.19 8.1 MANUAL START/STOP.19 8.1.1 PANEL START/STOP.19 8.1.2 REMOTE START/STOP.20 8.2 AUTO START/STOP.20 8.2.1 START CONDITIONS.20 8.2.1.1 INPUT START.20 8.2.1.2 GEN START MAINS NG.20 8.2.1.3 GEN START MASTER.20 8.2.2 GEN-GEN START/STOP.20 8.2.3 SCHEDULED RUN.22 8.2.4 SCHEDULED NOT RUN.23 9 PA
7、RAMETERS CONFIGURATION.24 9.1 ILLUSTRATION.24 9.2 PARAMETERS TABLE.24 9.3 DIGITAL INPUT/OUTPUT FUNCTION DESCRIPTION.35 9.3.1 INPUT PORTS FUNCTION.35 9.3.2 OUTPUT PORTS FUNCTION.37 9.3.3 CUSTOM COMBINED.40 9.4 DEFINITE TIME DELAY AND INVERSE DEFINITE MINIMUM TIME SETTING.41 10 HISTORICAL RECORDS.42 1
8、1 BLACK BOX RECORDS.43 12 SWITCH OPERATION.44 12.1 MANUAL OPERATION.44 12.2 AUTOMATIC OPERATION.46 13 ATS POWER SUPPLY.47 14 NEL CONTROL.48 14.1 ILLUSTRATION.48 14.2 AUTO OPERATION.48 14.3 MANUAL OPERATION.48 15 COMMUNICATION CONFIGURATION.49 16 TERMINALS.50 17 TYPICAL WIRING DIAGRAM.54 18 INSTALLAT
9、ION.56 19 TROUBLE SHOOTING.57 1 OVERVIEW HAT833 Series Three Power ATS Controller is intelligent tri-supply module with configurable function,automatic measurement,LCD display,and digital communication.It combines digitization,intelligence and networking.Automatic measurement and control can reduce
10、incorrect operation,which is an ideal option for ATS.The powerful Microprocessor contained within the unit allows for precision voltage(3-way 3-phase)measuring and make accurate judgment and the corresponding volt free digital output port will active when there is over/under voltage,over/under frequ
11、ency,loss of phase,phase sequence wrong and other abnormal condition occurs.It has compact structure,advanced circuits,simple wiring and high reliability,and can be widely used in electrical automatic control system of electric power,telecommunications,petroleum,coal,metallurgy,railways,municipal ad
12、ministration,intelligent building,etc.2 NAMING CONVENTION AND MODEL COMPARISON 2.1 NAMING CONVENTION Fig.1 Naming Convention 2.2 MODEL COMPARISON Table 2 Model Comparison Functions Model DC Supply AC Supply Sync.Closing Input Port No.Output Port No.RS485 HAT833 8 12 HAT833S 8 12 3 PERFORMANCE AND CH
13、ARACTERISTICS System type can set as:Mains-Mains-Gen,Mains-Mains-Mains,Mains-Gen-Gen,etc;4.3 inchs solid color 240 x128 LCD display with white backlight,multilingual interface(including English,Simplified Chinese or other languages),push-button operation;Collect and display 3-way 3-phase voltage,fre
14、quency and phase sequence;Collect and display load active power,reactive power,apparent power,power factor and current;S1/S2/S3 separated over current warning/trip alarm;NEL(Non-essential Load)trip function;Display S1/S2/S3 total kW energy,total kvar energy,total close times;Display continuous power
15、 supply time and S1/S2/S3 total power supply time;For Stored-Energy type ATS,its close relay will active after the PF Input is active;Over/under voltage,over/under frequency,over current,loss of phase,phase sequence wrong protection;Automatic/Manual mode.In manual mode,can force the switch to close
16、or open;All parameters can be set on site.Passwords authentication ensures authorized staff operation only;The genset can be manual test on site to achieve start/stop operation;Automatic re-closing;Closing output signal can be set as on intervals or as continuous output;Applicable for 3 isolated neu
17、tral line;Real-time clock(RTC);event log function(event log can record 200 items circularly);Scheduled routing run&scheduled not run(can be set as start genset once a day/week/month whether with load or not);Can control two generators to work as cycle run mode,master run mode and balance run mode;Wi
18、dely DC power supply range allows the controller can bear instantaneous 80V DC input;Large terminal space allows the controller can bear maximum 625V AC voltage input;With Dual-RS485 isolated communication interface.With remote controlling,remote measuring,remote communication,remote regulating func
19、tion by the ModBus-RTU communication protocol.Can remote start/stop the genset and remote control the breaker to close or open;Suitable for various AC systems(3-phase 4-wire,3-phase 3-wire,single-phase 2-wire,and 2-phase 3-wire);Modular design,self extinguishing ABS plastic shell,pluggable terminal,
20、built-in mounting,compact structure with easy installation.4 SPECIFICATION Table 3 Performance Parameters Items Contents Operating Voltage 1.DC8.0V35.0V,continuous power supply 2.AC(90305)V power supply A1N1/A2N2/A3N3 Power Consumption S2S3 8.2.3 SCHEDULED RUN Once“Scheduled Run”enables,users can se
21、t the scheduled start time.Controller will send start signal at preset start time.Start signal will deactivated after the start delay has expired.“Scheduled Run On Load”or“Scheduled Run Off Load”can be set.Scheduled Run On Load:When the input is active,genset close relay will active after genset is
22、normal.Scheduled Run Off Load:When the input is active,mains close relay will active after mains is normal.Cycle time of Scheduled Run can be set as start monthly,weekly and daily.Run Monthly:Which month to start,start date and time can be set.Run Weekly:Can start the genset at the same time in coup
23、le days of a week.Eg.Start the genset at 8:00 a.m.from Monday to Friday and keep 10 hours.Run Daily:Can start the genset at same time everyday.8.2.4 SCHEDULED NOT RUN Once”Scheduled Not Run”enables,users can set the“Scheduled Not Start”time.Start signal will deactivated at preset time and it will be
24、 inhibited before the delay has expired.Cycle time of“Scheduled Not Run”can be set as monthly,weekly and daily.Not Run Monthly:Which month not start,not start date and time can be set.Not Run Weekly:Can not start the genset at the same time in couple days of a week.Eg.Not Start the genset at 19:00 p
25、.m.from Monday to Friday and keep 12 hours.Not Run Daily:Can not start the genset at same time everyday.Note 5:“Scheduled Not Run”operation is prior to“Scheduled Run”operation.9 PARAMETERS CONFIGURATION 9.1 ILLUSTRATION In the main interface,press key,choose Configuration and press again to enter in