HMP300-S英文说明书.pdf
《HMP300-S英文说明书.pdf》由会员分享,可在线阅读,更多相关《HMP300-S英文说明书.pdf(20页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、 HMP300-S POWER INTEGRATED PROTECTION MODULE USER MANUAL All rights reserved.No part of this publication may be reproduced in any material form(including photocopying or storing in any medium by electronic means or other)without the written permission of the copyright holder.Applications for the cop
2、yright holders written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above.Any reference to trademarked product names used within this publication is owned by their respective companies.SmartGen Technology reserves the right to change
3、the contents of this document without prior notice.Table 1 Software Version Date Version Note 2020-11-20 1.0 Original release.CONTENTS 1 OVERVIEW.4 2 PERFORMANCE AND CHARACTERISTICS.4 3 SPECIFICATION.5 4 OPERATION.6 4.1 KEYS FUNCTION DESCRIPTION.6 5 SCREENS DISPLAY.6 5.1 POWER DATA DISPLAY.6 5.2 ALA
4、RM DISPLAY.7 5.3 MODULE INFORMATION DISPLAY.7 6 PROTECTION.7 6.1 WARNING.7 6.2 TRIP ALARM.8 7 WIRING CONNECTION.9 8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS.12 8.1 CONTENTS AND SCOPES OF PARAMETERS SETTING.12 8.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS 12.17 9 PARAMETERS SETTING.18 1
5、0 TYPICAL APPLICATION.19 11 INSTALLATION.20 1 OVERVIEW HMP300-S Power Integrated Protection Module integrates digital,intelligent and network technologies,is used to collect genset data(voltage,current,power and frequency)and output related actions for data errors,so as to protect the device.It fits
6、 with LCD display,optional Chinese and English bilingual interface,and it is reliable and easy to use.HMP300-S Power Integrated Protection Module adopts micro-processor technology to realize precise parameter measuring,fixed value adjustment functions etc.All parameters can be configured from front
7、panel or through LINK interface via PC.It can be widely used in all types of marine/land electrical device with compact structure,advanced circuits,simple connections and high reliability.2 PERFORMANCE AND CHARACTERISTICS Main features are as below:132x64 LCD display with backlight,optional language
8、 interface(Chinese and English),push-button operation;Equipped with LINK communication port;Through LINK interface on PC,data and parameters can be monitored and configured;Equipped with CANBUS port,which can connect with HMC9000/HMC6000 module to realize power and engine data collecting and display
9、ing at the same time;Differential protection function,and controller will issue related alarm information after differential protection is active;Protection for over/under voltage,over/under frequency,reverse power,over power and over current;Harmonic test function,and each phase voltage/current har
10、monic distortion rate can be tested;Suitable for 3-phase 4-wire,3-phase 3-wire,single phase 2-wire,and 2-phase 3-wire systems with frequency 50/60Hz;Collect and display 3-phase voltage,3-phase current,frequency and power parameters;Generator Line voltage (Uab,Ubc,Uca)Phase voltage(Ua,Ub,Uc)Frequency
11、 Hz Load Current Ia,Ib,Ic unit:A Each phase and total active power P unit:kW Each phase and total reactive power Q unit:kvar Each phase and average power factor PF Parameter setting function:users are allowed to set and change parameters and parameters shall be stored in internal FLASH memory and wo
12、uld not be lost even in case of power outage;most of them can be adjusted using front panel of the controller;Wide power supply range DC(835)V,suitable for different starting battery voltage environment;All parameters apply digital adjustment,instead of conventional analog modulation with normal pot
13、entiometer,improving the whole reliability and stability;With the 35mm guide rail mounting.3 SPECIFICATION Table 2 Technical Parameters Items Contents Operating Voltage DC8.0V to DC35.0V,continuous power supply Power Consumption 3W(standby 2W)AC Voltage Phase Voltage Range:AC1VAC380V(ph-N)Resolution
14、:0.1V Accuracy:0.5%Line Voltage Range:AC2VAC650V(ph-ph)Resolution:0.1V Accuracy:0.5%AC Frequency Range:41Hz 70Hz Resolution:0.01Hz Accuracy:0.5%AC Rated:5A Range:0A10A Resolution:0.1A Accuracy:0.5%Total Active Power Accuracy:0.5%Programmable Relay Output 1 5 A AC250V volt free output Programmable Re
15、lay Output 2 5 A AC250V volt free output Overall Dimension 107.6mm x 93mm x 60.7mm CT Secondary Current Rated:5A Working Conditions Temperature:(-25+70)C;Humidity:(2093)%RH Storage Condition Temperature:(-30+80)C Insulating Intensity Apply AC2.2kV voltage between high voltage terminal and low voltag
16、e terminal and the leakage current is not more than 3mA within 1min.Weight 0.3kg 4 OPERATION 4.1 KEYS FUNCTION DESCRIPTION Table 3 Keys Function Description Icons Function Description Set/Confirm Pressing this key will enter into password interface;In setting parameter status,pressing this key will
17、shift cursor or confirm the set value.Up/Increase Scrolls the screen up;Shift the cursor up or increase the set value in parameter setting menu.Down/Decrease Scrolls the screen down;Shift the cursor down or decrease the set value in parameter setting menu.Pressing both and simultaneously can reset a
18、larms.5 SCREENS DISPLAY 5.1 POWER DATA DISPLAY Table 4 Power Data Display 1st Screen Description ULL 380.1 380.1 380.1V ULN 220.2 220.2 220.2 V I:500.1 500.1 500.1 A P:276 kW Q:200 kvar PF 0.800 50.00Hz Line voltage Uab,Ubc,Uca Phase voltage Ua,Ub,Uc Current,Ia,Ib,Ic Active power,Reactive power Aver
19、age power factor,Frequency 2nd Screen Description P(kW)Q(kvar)S(kVA)A:89.0 65.0 110.0 B:89.0 65.0 110.0 C:89.0 65.0 110.0 PF 0.800 0.800 0.800 Active power display、Reactive power display、Apparent power display A phase:active power,reactive power,apparent power B Phase:active power,reactive power,app
20、arent power C Phase:active power,reactive power,apparent power A phase,B phase and C phase power factors 3rd Screen Description THDu(%)THDi(%)A:0.5 0.3 B:0.5 0.3 C:0.5 0.3 Phase Seq 0 120 240 Voltage harmonic distortion rate,current harmonic distortion rate A phase:voltage harmonic distortion rate,c
21、urrent harmonic distortion rate B phase:voltage harmonic distortion rate,current harmonic distortion rate C phase:voltage harmonic distortion rate,current harmonic distortion rate Phase sequence 4th Screen Description Total kWh 696.1 kWh Total kvarh 425.8 kvarh kWh%103%kvarh%246.6%Total active energ
22、y Total reactive energy Active power percentage Reactive power percentage 5.2 ALARM DISPLAY All alarm information(trip alarm and warning alarm)collected by the module is real-time displayed on the alarm interface as bellow:Table 5 Alarm Display Display Description Alarm Warning Alarm Under Voltage W
23、arning Title Alarm type Alarm content 5.3 MODULE INFORMATION DISPLAY Module information include output port status,software version,hardware version and release time can be displayed on this interface as bellow:Table 6 Module Information Display Display Description OUT:1 2 Software Version:V1.0 Hard
24、ware Version:V1.3 Issue Date:2020-11-20 Number of output port Outputs Status Software version Hardware version Release date 6 PROTECTION 6.1 WARNING When controller detects the warning signals,alarm indicator flashes and LCD displays the warning information.Table 7 Module Warning Types No.Type Descr
25、iption 1 Over Volt Warning When the module detects that the genset voltage is greater than the pre-set value,it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.2 Under Volt Warning When the module detects that the genset voltage is less than the pre-set