1、Approval StandardforFire Pump Flowmeter SystemsClass Number 1046January 19872002 FM Global Technologies LLC.All rights reserved.ForewordFM Approvals are intended to verify that the products and services described will meet stated conditions ofperformance,safety and quality useful to the ends of prop
2、erty conservation.The purpose of FM ApprovalStandards is to present the criteria for FM Approval of various types of products and services,as guidance forFM Approvals personnel,manufacturers,users and authorities having jurisdiction.Products submitted for Approval shall demonstrate that they meet th
3、e intent of the Approval Standard,and thatquality control in manufacturing and/or applications shall ensure a consistently uniform and reliable product orservice.FM Approval Standards strive to be performance-oriented and to facilitate technological development.For examining equipment,materials and
4、services,FM Approval Standards:a)must be useful to the ends of property conservation by preventing,limiting or not causing damageunder the conditions stated by the Approval listing;andb)must be readily identifiable.Continuance of Approval and Listing depends on compliance with the Approval agreement
5、,satisfactoryperformance in the field,on successful re-examinations of equipment,materials,and services as appropriate,andon periodic follow-up audits of the manufacturing facility or service/application.FM Global Technologies LLC reserves the right in its sole judgement to change or revise its stan
6、dards,criteria,methods,or procedures.TABLE OF CONTENTSI.INTRODUCTION.11.1 Purpose.11.2 Scope.11.3 Basis for FM Approval.11.4 Basis for Continued Approval.11.5 Requirements.11.6 Effective Date.21.7 System of Units.2II.GENERAL INFORMATION.22.1 Product Information.2III.GLOSSARY.2IV.GENERAL REQUIREMENTS
7、(OTHER THAN PERFORMANCE REQUIREMENTS).34.1 Minimum Meter Size.34.2 Flow Measurement Device.44.3 Markings.44.4 Instructions.44.5 Physical or Structural Features.44.6 Drawings/Plans/Specifications Required.44.7 Other Requirements.5V.PERFORMANCE REQUIREMENTS.55.1 Operation and Accuracy.55.2 Hydrostatic
8、 Strength.55.3 Friction Loss Determination.6VI.MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS.66.1 Demonstrated Quality Control Program.66.2 Facilities and Procedures Audit(F&PA).7APPENDIX A:APPROVAL MARKS.8APPENDIX B:UNITS OF MEASUREMENT.9I.INTRODUCTION1.1 PurposeThis standard states FM Approval
9、 requirements for fire pump flowmeter systems used to determine the dischargeof a fire pump.1.2 ScopeThere are many devices and methods for measuring the flow of liquids through a pipeline.The devices examinedto the requirements of this standard shall be specificallyApproved for use on fire pump sys
10、tems,and a particularmodel or models shall be specified for a particular pump size.1.3 Basis for FM ApprovalFM Approval is based upon satisfactory evaluation of the product and the manufacturer in the following majorareas:1.3.1 Examination and tests on production samples shall be performed to evalua
11、te the suitability of the product;and the proper operation and performance of the product as specified by the manufacturer and required byFM Approvals.1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made toevaluate the manufacturers ability to pr
12、oduce the product which is examined and tested,and the markingprocedures used to identify the product.These examinations are repeated as part of FM Approvalsproductfollow-up program.1.4 Basis for Continued ApprovalContinued Approval is based upon:production or availability of the product as currentl
13、y Approved;the continued use of acceptable quality control procedures;satisfactory field experience;compliance with the terms stipulated in the Approval Agreement;and re-examination of production samples for continued conformity to requirements.1.5 Requirements1.5.1 The requirements of this standard
14、 are based on experience,research and testing and/or the standards ofother national and international organizations.The advice of manufacturers,users,trade associations andloss control specialists was also considered.1.5.2 Meeting these requirements qualifies a product as an Approved fire pump flowm
15、eter system.January 19871046FM APPROVALS11.5.3 The requirements of this standard reflect tests and practices used to examine characteristics of fire pumpflowmeter systems for the purpose of obtaining FM Approval.These requirements are intended primarilyas guides,and strict conformity is not always m
16、andatory.Fire pump flowmeter systems having charac-teristics not anticipated by this standard may beApproved if performance equal or superior to that requiredby this standard is demonstrated,or if the intent of the standard is met.Alternatively,flowmeters whichdo meet all the requirements identified
17、 in this standard may not be Approved if other conditions whichadversely affect performance exist or if the intent of this standard is not met.1.6 Effective DateThe effective date of anApproval standard mandates that all products tested forApproval after the effective dateshall satisfy the requireme
18、nts of that standard.ProductsApproved under a previous edition shall comply with thenew version by the effective date or else forfeit Approval.The effective date shall apply to the entire Approvalstandard,or,where so indicated,only to specific paragraphs of the standard.1.7 System of UnitsUnits of m
19、easurement are English System standard units.These are followed by their arithmetic equivalents inInternational System(SI)units,enclosed in parentheses.Appendix B lists the selected units for quantities dealtwith in testing these products;conversions to SI units are included.Conversion of U.S.custom
20、ary units is inaccordance with ASTM E380.II.GENERAL INFORMATION2.1 Product InformationFire pump flowmeter systems are used to measure the flow output of fire pumps during testing;when installedthey perform the same function as a system of 212inch fire hose and playpipes.The system is permanentlyinst
21、alled in a pipeline which connects the discharge of the pump to the suction supply of the pump or to drainfacilities.The system is isolated from the pump discharge during pump operations other than flow testing.III.GLOSSARYFor purposes of this standard,the following terms apply:Flow Element The flow
22、 element is that part of the system which is permanently installed in the meterline.The device generates a signal(i.e.,a secondary flow,a pressure differential,an electrical signal,orother)which is proportional to the flow of water discharging from the pump and which is sent to the flowmeasurement d
23、evice.The flow element may be a venturi tube,orifice plate,magnetic meter,pilot tube,orother device,and may be made up of a combination of these devices.1046January 19872FM APPROVALSFlow Measurement Device The flow measurement device is that part of the system which displays thesignal produced by th
24、e flow element as a flow rate.This instrument may be portable or permanentlyinstalled.The flow measuring instrument may be a manometer,a differential meter with linear or squareroot scale,a rotameter,an electrical meter,or other readout device.IV.GENERAL REQUIREMENTS(OTHER THAN PERFORMANCE REQUIREME
25、NTS)4.1 Minimum Meter Sizea)The following minimum meter sizes(nominal pipe size of the meter line)shall be observed:Pump RatingMeter Line Sizegal/min(dm3/min)inchesmm200(760)3(76)250(950)3.5(89)300(1140)3.5(89)450(1710)4(102)500(1890)5(127)750(2830)5(127)1000(3790)6(152)1250(4730)6(152)1500(5675)8(2