FM认证的消防标准资料 Acr18Ftmp.pdf
《FM认证的消防标准资料 Acr18Ftmp.pdf》由会员分享,可在线阅读,更多相关《FM认证的消防标准资料 Acr18Ftmp.pdf(13页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、Approval StandardforIndicator PostsClass Number 1110November 1990(Replaces July 1975)2002 FM Global Technologies LLC.All rights reserved.ForewordFM Approvals are intended to verify that the products and services described will meet stated conditions ofperformance,safety and quality useful to the end
2、s of property conservation.The purpose of FM ApprovalStandards is to present the criteria for FM Approval of various types of products and services,as guidance forFM Approvals personnel,manufacturers,users and authorities having jurisdiction.Products submitted for Approval shall demonstrate that the
3、y meet the intent of the Approval Standard,and thatquality control in manufacturing and/or applications shall ensure a consistently uniform and reliable product orservice.FM Approval Standards strive to be performance-oriented and to facilitate technological development.For examining equipment,mater
4、ials and services,FM Approval Standards:a)must be useful to the ends of property conservation by preventing,limiting or not causing damageunder the conditions stated by the Approval listing;andb)must be readily identifiable.Continuance of Approval and Listing depends on compliance with the Approval
5、agreement,satisfactoryperformance in the field,on successful re-examinations of equipment,materials,and services as appropriate,andon periodic follow-up audits of the manufacturing facility or service/application.FM Global Technologies LLC reserves the right in its sole judgement to change or revise
6、 its standards,criteria,methods,or procedures.TABLE OF CONTENTSI INTRODUCTION.11.1 Purpose.11.2 Scope.11.3 Basis for FM Approval.11.4 Basis for Continued Approval.11.5 Basis for Requirements.11.6 Effective Date.21.7 System of Units.2II GENERAL INFORMATION.2III GENERAL REQUIREMENTS.23.1 Materials.23.
7、2 Barrel.33.3 Post Cap.33.4 Operating Stem.33.5 Target Mechanism.43.6 Extension Rod.43.7 Wrench or Handwheel.43.8 Locking and Sealing.53.9 Markings.53.10 Drawings/Plans/Specifications Required.6IV PERFORMANCE REQUIREMENTS.64.1 Visibility.64.2 Weatherability.64.3 Torque,Vertical Indicator Posts.74.4
8、Torque,Wall Type Indicator Posts.74.5 Nonmetallic Components.74.6 Other Tests.7V OPERATIONS REQUIREMENTS.85.1 Demonstrated Quality Control Program.85.2 Facilities and Procedures Audit(F&PA).8APPENDIX A:APPROVAL MARKS.9APPENDIX B:UNITS OF MEASUREMENT.10I INTRODUCTION1.1 PurposeThis Standard states FM
9、 Approval requirements for indicator posts.1.2 Scope1.2.1 This standard sets performance requirements for indicator posts.Indicator posts are controls,extendingaboveground or through building walls,for operating gate valves used in fire protection systems.Animportant feature of their design is a tar
10、get indicator,visible through an opening in the post,which isprovided to show whether the valve is open or shut.1.2.2 This standard applies to both wall and vertical type indicator posts for use in operating inside-screw gatevalves.1.3 Basis for FM ApprovalFM Approval is based upon satisfactory eval
11、uation of the product and the manufacturer in the following majorareas:1.3.1Examination and tests on production samples shall be performed to evaluate the suitability of the product;the proper operation and performance of the product as specified by the manufacturer and required byFM Approvals;and,a
12、s far as practical,the durability and reliability of the product.1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made toevaluate the manufacturers ability to produce the product which is examined and tested,and the markingprocedures used to ident
13、ify the product.These examinations are repeated as part of FM Approvalsproductfollow-up program.1.4 Basis for Continued ApprovalContinued Approval is based upon:production or availability of the product as currently Approved;the continued use of acceptable quality control procedures;satisfactory fie
14、ld experience;compliance with the terms stipulated in the Approval Agreement;and re-examination of production samples for continued conformity to requirements.1.5 Basis for Requirements1.5.1 The requirements of this standard are based on experience,research and testing and/or the standards ofother n
15、ational and international organizations.The advice of manufacturers,users,trade associations andloss control specialists was also considered.November 19901110FM APPROVALS11.5.2 The requirements of this standard reflect tests and practices used to examine characteristics of indicatorposts for the pur
16、pose of obtaining FM Approval.These requirements are intended primarily as guides,andstrict conformity is not always mandatory.Indicator posts having characteristics not anticipated by thisstandard may be Approved if performance equal or superior to that required by this standard is demon-strated,or
17、 if the intent of the standard is met.Alternatively,indicator posts that do meet all the require-ments identified in this standard may not be Approved if other conditions which adversely affectperformance exist or if the intent of this standard is not met.1.6 Effective DateThe effective date of anAp
18、proval Standard mandates that all products tested forApproval after the effective dateshall satisfy the requirements of that standard.ProductsApproved under a previous edition shall comply with thenew version by the effective date or else forfeit Approval.The effective date shall apply to the entire
19、 ApprovalStandard,or,where so indicated,only to specific paragraphs of the standard.The effective date of this Standard is July 1,1991 for full compliance with all requirements.1.7 System of UnitsUnits of measurements are English System standard units.These are followed by their arithmetic equivalen
20、ts inInternational System(SI)units,enclosed in parentheses.Appendix B lists the selected units for quantities dealtwith in testing these products;conversions to SI units are included.Conversion of U.S.customary units is inaccordance with ASTM E380.II GENERAL INFORMATION2.1 The indicator post consist
21、s of a barrel,a flanged extension which allows the height at the barrel to beadjusted and a stem which operates the underground valve and simultaneously moves the target.To permitturning the stem from a constant height,a telescoping union is commonly employed.III GENERAL REQUIREMENTS3.1 MaterialsAll
22、 materials used in the construction of indicator posts shall be suitable for the intended application.Partsexposed to water shall be resistant to corrosion.Nonmetallic components shall be considered fornon-stress-bearing applications if tested to the requirements of Paragraph 4.5.1110November 19902F
23、M APPROVALS3.2 Barrel3.2.1 The barrel shall be of such material and thickness as to provide adequate strength and corrosion resistance.A typical material is cast iron with a38in.(9.6 mm)wall thickness.3.2.2 Sufficient clearance between the post inside the wall and the operating stem,target mechanism
24、,valveoperating nut and other moving parts shall be provided.3.2.3 The length of the barrel for underground valves shall be such that the middle of the target windows shallbe at least 30 in.(762 mm)above the intended ground level.3.2.4 A suitable seal shall be provided to minimize the possibility of
25、 water entering between two telescopingsections that form an adjustable barrel for application with underground valves.This may be accomplishedby extending the upper part below the ground a distance of not less than 10 in.(254 mm)and telescopingover the lower part which projects above the bury line.