阀门规格SPECIFICATION OF 2ND LOTS.pdf
《阀门规格SPECIFICATION OF 2ND LOTS.pdf》由会员分享,可在线阅读,更多相关《阀门规格SPECIFICATION OF 2ND LOTS.pdf(8页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、Section VI Schedule of Requirements 88 LOT NO.2 SUPPLY OF VALVES,HYDRANTS,COUPLINGS AND ACCESSORIES 3.PARTICULAR REEQUIRMENTS FOR LOT NO.2 3.1 Item B.1 Gate Valve The following particular requirements are specified for the following items:Line Item No.Description of Goods Quantity Physical Unit B.1.
2、a Gate Valve;with flanges for pipe diam.DN 80mm 85 Nr.B.1.b As above;DN 100mm 75 Nr.B.1.c As above;DN 150mm 55 Nr.B.1.d As above;DN 200mm 25 Nr.B.1.e As above;DN 250mm 20 Nr.B.1.f As above;DN 300mm 20 Nr.Gate Valves shall be resilient-seat type.Operation shall be manual,Clockwise-to-Close,by T-key.A
3、 full circle axial bearing system shall make the operation easy with no need for excess force.The valve design shall provide full-bore clearance when the valve is fully open,with the shoulders of the gate sealing against the valve bonnet.The valve design shall allow the valve bonnet to be removed fo
4、r inspection purpose,without having to remove the valve body from the pipe line.Stem sealing shall be by O-rings,which can be replaced under pressure with the gate fully raised.Gate Valves shall have PN16 pressure rating,with design according to BS EN 1074-1&2:2000 requirements and BS 5163-1:2004 re
5、quirements,and to WRAS requirements for potable water use,with bodies and bonnets made of Ductile Iron subject to BS EN 1563:2011 standard,with internal and external,fusion bonded,blue two-pack epoxy coating according to WIS 4-52-01 Class B(250 microns)requirements.Gate Valves shall have wedges made
6、 of Ductile Iron subject to BS EN 1563:2011 standard.Wedges shall be fully encapsulated in EPDM rubber which is suitable for potable water and resistant to chlorine.The rubber coating of the wedge shall be applied by a vulcanization process,with a layer thickness of minimum 4mm on seating areas and
7、minimum 1.5mm on other surfaces.Gate Valves shall have stems made of Stainless Steel subject to BS EN 10088-1:2014 standard.The transport thread shall be rolled onto the stem in a trapezoidal profile according to DIN 103-1:1977 requirements.The upper part of the thread shall terminate in a way that
8、when the fully open position is reached,but before the wedge touches the inner coating,the wedge stops abruptly and blocks further turning of the stem.Gate Valves shall have stem seals consisting of three systems:(a)innermost a lip seal in EPDM rubber shall act as main seal against the internal flui
9、d pressure;(b)in the middle the radial bearing O-rings shall back up the inner main seal;and(c)outermost an NBR rubber wiper ring shall seal against dust and dirt from outside.Section VI Schedule of Requirements 89 Gate Valves shall have the following information cast onto the body surface:Manufactu
10、rer Flow direction arrow Cast material DN diameter class PN pressure class Gate Valves shall have flange joints which meet BS EN 1092-2:1997 requirements for PN16 pressure rating.The bolt holes shall be wax-filled.Gate Valves shall be provided complete,with 2 Nr.Flange Gaskets,and 2 Sets of Nuts,Bol
11、ts and Washers,which are provided separately under Items B.9 and B.10 respectively.3.2 Item B.2 Single Small Orifice Air Valve The following particular requirements are specified for the following items:Line Item No.Description of Goods Quantity Physical Unit B.2 Single Small Orifice Air Valve;with
12、flange for pipe diam.DN 80mm 35 Nr.Single Small Orifice Air Valves are valves,which automatically release small quantities of air from water mains under normal working pressure,thus allowing this excess air out of the water main,while containing the water within the pipe during operation.The valves
13、have float mechanisms,which sense the presence of air and cause the float mechanisms to open the valve orifices,which release the air from the water main.Single Small Orifice Air Valves shall have PN16 pressure rating,with design according to BS EN 1074-1&4:2000 requirements,and to WRAS requirements
14、 for potable water use,with bodies and bonnets made of Ductile Iron subject to BS EN 1563:2011 standard,with internal and external,fusion bonded,blue two-pack epoxy coating according to WIS 4-52-01 Class B(250 microns)requirements.Single Small Orifice Air Valves shall have flange joints which meet B
15、S EN 1092-2:1997 requirements for PN16 pressure rating.The bolt holes shall be wax-filled.Each Single Small Orifice Air Valve shall be provided complete,with 2 Nr.Flange Gaskets,and 2 Sets of Nuts,Bolts and Washers,which are provided separately under Item B.9 and Item B.10 respectively.3.3 Item B.3
16、Double Orifice Air Valve The following particular requirements are specified for the following items:Line Item No.Description of Goods Quantity Physical Unit B.3 Double Orifice Air Valve;with flange for pipe diam.DN 80mm 65 Nr.Section VI Schedule of Requirements 90 Double Orifice Air Valves are valv
17、es,which have a large orifice for ventilation or exhaust of a water main,and which have another smaller orifice for automatic release of air under normal working pressure.Double Orifice Air Valves shall be capable of automatically exhausting air from water mains when being filled,the air being relea
18、sed at a sufficiently high rate to prevent the restriction of the filling rate.The valves shall also automatically release air accumulating in water mains during normal working conditions.The valves shall be designed to prevent premature closure prior to all air having been discharged from the water
19、 main.Double Orifice Air Valves shall also be capable of ventilating water mains automatically when being emptied,the air inflow rate being sufficiently high to prevent the development of a vacuum in the water mains.Orifices shall be positively sealed in the closed position,but the floats shall only
20、 be raised by the water and not by a mixture of air and water spray.The seating of floats shall be designed to prevent the floats from sticking after long periods in the closed position.Double Orifice Air Valves shall have PN16 pressure rating,with design according to BS EN 1074-1&4:2000 requirement
21、s,and to WRAS requirements for potable water use,with bodies and bonnets made of Ductile Iron subject to BS EN 1563:2011 standard,with internal and external,fusion bonded,blue two-pack epoxy coating according to WIS 4-52-01 Class B(250 microns)requirements.Double Orifice Air Valves shall have flange
22、 joints which meet BS EN 1092-2:1997 requirements for PN16 pressure rating.The bolt holes shall be wax-filled.Each Double Orifice Air Valve shall be provided complete,with 2 Nr.Flange Gaskets,and 2 Sets of Nuts,Bolts and Washers,which are provided separately under Item B.9 and Item B.10 respectively
23、.3.4 Item B.4 Fire Hydrant The following particular requirements are specified for the following items:Line Item No.Description of Goods Quantity Physical Unit B.4 Fire Hydrant;with flange for pipe diam.DN 80mm 100 Nr.Fire Hydrants shall be underground fire hydrants of BS 750:2012 Type 1 standard,sc
24、rewed-down type with screwed 2-1/2”round thread outlet,according to BS EN 14339:2005 and BS EN 1074-1&6:2000&2008 requirements,and to WRAS requirements for potable water use.Fire Hydrants shall have PN16 pressure rating,with bodies and bonnets made of Ductile Iron subject to BS EN 1563:2011 standard
25、,with corrosion resistance for disinfection products,with internal and external,fusion bonded,blue two-pack epoxy coating according to WIS 4-52-01 Class B(250 microns)requirements.Fire Hydrants shall be fully maintainable,with minimum flow requirements of 2000 litres per minutes for Kv=90 and 2470 l