1、 1“Fault arc”model 1.Introduction Although three-phase bus fault is the most serious fault on transmission lines,experiences and statistical data indicate that the Single Phase to Ground(SLG)is the most common fault,especially in EHV transmission systems.An arc occurs during SLG fault.It can be clas
2、sified into the primary arc duration(before breakers open)and the secondary arc duration(after the breakers trip).In the primary arc duration,the heavy short circuit current flows through the primary arc,and there is no significant elongation of the arc.In the secondary arc duration,the faulted phas
3、e is isolated from both ends by the related protective relays and single pole breakers.The faulted conductor(line)is capacitively and inductively coupled to the two sound conductors and other conductors of parallel circuits(ex.Double circuit lines),which are still energized at approximately normal c
4、ircuit voltage and carrying load current.This coupling has two effects 1:Before the extinction of the fault arc,it feeds current to the fault and maintains the arc.After the arc current becomes zero,the coupling causes a recovery voltage across the arc path.If the rate of rise of recovery voltage is
5、 too great,it will reignite the arc.The secondary is the dominant fact of the arc extinction.A detailed fault arc model is extremely important for the fault transient studies such as auto-reclosure and protection design.This report introduces a fault arc component developed in PSCAD/EMTDC based on t
6、he model proposed by A.T.Johns 2.The mathematic arc model is introduces first,then a component based on the model in PSCAD/EMTDC is introduced,finally validation and applications of this component are conducted.2 2.The Mathematic Model of Fault Arc From a modelling point of view,the fault arc can be
7、 classified as the high current primary arc during the fault and the low current secondary arc(after the faulted phase is isolated)and which is sustained by mutual coupling between the healthy and faulted phases.The details of primary and secondary arc models refer 2.This report only gives a brief i
8、ntroduction on them.2.1.Model of primary arc The arc conductance is a time variable.=Where:time varying primary arc conductance:stationary primary arc conductance:primary arc time constant:peak value of primary arc current :a coefficient 2.85e-5 Subscripts:p:primary 2.2.Model of secondary arc 2.2.1.