1、Electrical Equipment and Operation1ContentsThe Working Principle of Electromagnetic Current TransformerThe Influence of the Open Circuit on the Secondary Side of the Current TransformerPolarity and Wiring Method of Current TransformerONThe current transformer turns a large current into a small curre
2、nt(5A or 1A),which is used as the AC power supply and current signal of measuring instruments and relays.Electromagnetic current transformers are widely used in power systems,represented by TA(the old symbol is CT or LH).Overview of Current Transformers3The Working Principle and Characteristics of E
3、lectromagnetic Current TransformerThe current transformer also works according to the principle of electromagnetic induction.Its structure is similar to that of an ordinary transformer,mainly composed of iron core,primary winding and secondary winding.Fig.3-1 Principle structure diagram and wiring d
4、iagram of current transformer(a)Principle structure diagram (b)Wiring diagramThe ratio of the primary and secondary rated currents of the current transformer is called the rated transformation(current)ratio Ki of the current transformer,which can be expressed as:The secondary rated current of the cu
5、rrent transformer has two types:5A and 1A.Generally,5A is used for high-current system,and 1A for weak-current system.1A can also be considered when the power distribution device is far from the control room.At present,the primary rated current levels of current transformers are:5,10,15,20,30,40,50,
6、75,100,150,200,300,400,600,800,1000,1200,1500,2000,3000,4000,5000,6000,8000,10000,15000,20000,25000A.5The Working Principle and Characteristics of Electromagnetic Current Transformer(1)The primary winding is connected in series in the tested circuit with few turns.The current in the primary winding
7、completely depends on the current of the tested circuit,and has nothing to do with the secondary current.Fig.3-1 Principle structure diagram and wiring diagram of current transformer(a)Principle structure diagram (b)Wiring diagram(2)The secondary winding has many turns,and the resistance of the curr
8、ent coil of the instrument or relay connected in series is very small,so during normal operation,the secondary side of the current transformer is close to working in a short-circuit condition.6The Influence of the Open Circuit on the Secondary Side of the Current TransformerFor current transformers
9、in operation,the secondary circuit must be connected to a load or be directly short-circuited,and no open circuit is allowed.nIn normal state:nAnalysis:F2 plays the role of demagnetizing F1,and the role of F0 is very small;nIn an open circuit:F20,nWhen F1 is unchanged,F0 will be very large,the core
10、is saturated,and becomes a flat-top wave.To voltage transformer7 7The Influence of the Open Circuit on the Secondary Side of the Current TransformerFor current transformers in operation,the secondary circuit must be connected to a load or be directly short-circuited,and no open circuit is allowed.Co