[信息与通信]某半导体分立器件封装测试厂厂务能源管理系统介绍课件.ppt
《[信息与通信]某半导体分立器件封装测试厂厂务能源管理系统介绍课件.ppt》由会员分享,可在线阅读,更多相关《[信息与通信]某半导体分立器件封装测试厂厂务能源管理系统介绍课件.ppt(34页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、Energy Statistics&ManagementSystemVishay Micro-electronics(Xian)Co.,Ltd.January 16,2008IEHS/FSD Cost Reduction Plan General Description of Energy Administration SystemEnergy supply specificationlOutsourcing specificationlSupply specification User energy management systemlEstablish tree chart of ener
2、gy supply systemlApplication system for user demand modification or addition.lEnergy management for temporary user.Oct 12,20072IEHS/FSD Cost Reduction Plan General Description of Energy Administration SystemEnergy statistics&analysis system.lRoutine record of energy consumptionlWeekly statistics of
3、energy consumptionlAnalysis on weekly statistics dataQuantity of energy consumptionCost of energy consumptionCost per k products for each outsourcing energies.Energy cost per k productslFeed back abnormal data to relevant personnel of production,maintenance and IEHS to find the reason.ReportinglProv
4、ide energy statistics data to finance.lReport energy statistics data to Asia IEHS director.Oct 12,20073IEHS/FSD Cost Reduction Plan Energy outsourcing specificationNo.ItemSpecificationSupplierRemarks1Power50Hz,3 phase,10KV10Municipal Bureau of Power SupplyState Grid Northwest Company2N2 Bulk nitroge
5、n tank,purity not less than 99.999,Dew point-60,Oxygen less than 10PPMTaida Low Temperature Equipment Co.,Ltd.3H2Cylinder,purity not less than 99.999,Dew point-60,Oxygen less than 10PPMTaida Low Temperature Equipment Co.,Ltd.4Tap waterP0.3MPa,quality to meet relevant standard of drinking water quali
6、tyMunicipal Utility ServiceMunicipal Utility pipeline5Natural gasP8KPa,methane not less than 94%(V/V),Low Heat Value not less than 33MJ/Nm3Qinhua Natural Gas Co.,Ltd.Municipal Utility pipelineOct 12,20074IEHS/FSD Cost Reduction Plan Energy supply specificationNo.ItemTypeSpecificationRange of SupplyR
7、emarks1Power3 phase 380VAC50Hz,3 phase 380V,10All building(Except for office)1.Plug-in Bus supply in Production area21phase 220VAC50Hz,1phase 220V,10All building 2.TN-S power supply system33 phase 380V EPS50Hz,3 phase 380V,10Fire fighting,EPS,exhaust scrubber system3.Beaker+terminal connection shall
8、 be used if power load more than 5 Kw.Power socket could be used when load less than 5Kw4Normal lighting400LUXOffice,control room,warehouse1.The luminance of fluorescent lamp reduces slowly.IEHS makes plan to replace regularly.5600LUXProduction area,lab,IQC2.Lux of Emergency lighting will be lower t
9、han normal.6200LUXHall way3.The luminance of outdoor and exterior walls lighting complies with relevant specification.7Emergency lighting50LUXOther individual building,emergency lighting of each room4.Emergency exit indication lamps installed 8GasNitrogenPurity not less than 99.999,Pressure 0.70.85M
10、Pa(system pressure)Dew point lower than-60,Oxygen content less than 10PPMDI water station,FG warehouse,Reliability Lab,FE Lab,Die Bank,IQC,FOL/Mold/Solder Dip area.9Forming gasN2:89%87%,H2:11%13%,pressure 0.340.41MPa(system pressure),Dew point less than-60,Oxygen content less than 10PPMDie bond10Com
11、pressed air0.60.7MPa,压力露点不大于+5,经精密过滤Reliability Lab,FOL/Mold/Solder Dip/testing/plating area11VacuumVacuum0.8BarFOL12SteamPressure 0.30.4barHeating of Facility station,Facility office and control room,heating and humidification of AHU,heat supply of FCU heat exchanger.Oct 12,20075IEHS/FSD Cost Reduc
12、tion Plan Energy supply specificationNo.ItemTypeSpecificationRange of SupplyRemarks13Feed&DischargeProcess cooling water0.2MPa0.3MPa,28Mold/Solder Dip,Test area,Rel.LabTotal hardness less than 5PPM14DI waterResistance15M,0.MPaMold/Solder Dip,Test area,calibration Lab,Rel.Lab,FE Lab,Plating15Hot wate
13、r0.15MPa,4060Toilets(main building)and kitchen16Tap water0.2MPaSolder Dip,Plating,Toilets,Kitchen,FE Lab,Rel.Lab,Calibration LabFor eyewash and water replenishment&washing of some equipment17Industrial wastewater dischargeDischarged directly,max.flow 7.5M3/HDI water Station,FOL,Solder Dip,FE Lab,Rel
14、iability Lab,Kitchen.18Domestic Wastewater dischargeDischarged through oil separation/septic tankToilets and kitchen19Industrial wastewater dischargeDischarged after waste water treatmentPlating20HVACAmenity air conditionerT=1825Offices,Meeting room,cafeteria,training room.21Industrial air condition
15、er1.T&H:TestingT=25,2,RH=4060,Plating T=23,2,RH=3070%,others T=25,5,RH=4060%;2.Pressure difference:Mold,Solder Dip,Plating:negative pressure(-105Pa),FOL,Testing,Die Bank:positive pressure(+105Pa);Lab(05Pa)3.Cleanliness:ISO 8 level in K1 area and ISO 9 level in other area.FOL,Mold,Solder Dip,Test,Pla
16、ting,Dise Bank,IQC,Rel.Lab,FE Lab,Calibration LabOct 12,20076IEHS/FSD Cost Reduction Plan User Energy Management 1Establish tree chart of each kind of energy suppliesFacility supply pipelines system diagramUser of each main lines and branchesCapacity of each main lines and branchesOccupied capacity
17、of each main lines and branches can be calculated automatically based on equipment installation information.If occupied capacity of one supply line reaches 80%of design capacity,alarm will be given in the system that no end equipment shall be added in this line.Oct 12,20077IEHS/FSD Cost Reduction Pl
18、an Supply pipe&line system diagram Oct 12,20078IEHS/FSD Cost Reduction Plan Facility supply system diagramOct 12,20079IEHS/FSD Cost Reduction Plan Facility supply system diagramOct 12,200710IEHS/FSD Cost Reduction Plan Facility supply system diagramPower system is analyzed by logistic sheetOct 12,20
19、0711IEHS/FSD Cost Reduction Plan User energy management 2Establish Application Form for supply demand changeApplication for supply increase or change.Ensure supply change will not affect facility system negatively.Insufficient capacity of supply linesDue to user equipment addition,some equipment aff
20、ects other equipment negatively.Review facility supply system while user equipment capacity increase.Oct 12,200712IEHS/FSD Cost Reduction Plan StartUser submit technical specification to confirm technical requirement and supply demandUser submit Applicarion form for Facility Supply IncreaseIEHS revi
21、ew the system capacity and make assessmentFeasibleIEHS manager approve and sign on technical specificationYESNOPR and PurchasePlan to be modifiedYESSupply upgradingEndNOIs supply to be increasedInstallationYESNOPlant GM approveProcess of Supply Increase ApplicationOct 12,200713IEHS/FSD Cost Reductio