《35kV线路侧CT新安装试验报告.docx》由会员分享,可在线阅读,更多相关《35kV线路侧CT新安装试验报告.docx(4页珍藏版)》请在淘文阁 - 分享文档赚钱的网站上搜索。
1、1设备参数设备单 元相别型号出厂日期出厂编号生产厂家绕组编号变比级别罗31 开关 CTA相LZZBJ9-40.5WXXXXXXXXXXXXXXX1S1-1S2200/55P201S1-1S3400/55P201S1-1S4600/55P202S1-2S2200/55P202S1-2S3400/55P202S1-2S4600/55P203S1-3S2200/50. 53S1-3S3400/50. 53S1-3S4600/50. 54S1-4S2200/50. 2S4S1-4S3400/50. 2S4S1-4S4600/50. 2SB相LZZBJ9-40.5W1S1-1S2200/55P201S1
2、-1S3400/55P201S1-1S4600/55P202S1-2S2200/55P202S1-2S3400/55P202S1-2S4600/55P203S1-3S2200/50. 53S1-3S3400/50. 53S1-3S4600/50. 54S1-4S2200/50. 2S4S1-4S3400/50. 2S4S1-4S4600/50. 2SC相LZZBJ9-40.5W1S1-1S2200/55P201S1-1S3400/55P201S1-1S4600/55P202S1-2S2200/55P202S1-2S3400/55P202S1-2S4600/55P203S1-3S2200/50.
3、 53S1-3S3400/50.53S1-3S4600/50. 54S1-4S2200/50. 2S4S1-4S3400/50. 2S4S1-4S4600/50. 2S2试验仪器仪表名 称型号编号级别电子摇表2.0级电流表0.5级电流表0.5级电流表0.5级CT综合测试仪器0.5级3试验依据序号试验依据名称1继电保护及电网安全自动装置检验条例2GB 7261-2016继电器及继电保护装置基本试验方法3GB 14285-2006继电保护和安全自动装置技术规程4DL/T 995-2016继电保护和电网自动装置检验规程4试验人员试验日期环境温度试验人员记录人录入人工作负责人CT新安装试验报告1 极性
4、检查二次 绕组 编号A相B相C相母线P1+线路/主变P2-极性回路用途极性回路用途极性回路用途1S1+A411保护+B411保护+C411保护1S21S31S4N411N411N4112S1+A421保护(备用)+B421保护(备用)+C421保护(备用)2S22S3一2S4N421421N4213S1+A431测量(备用)+B431测里(备用)+C431测量(备用)3S23S3一3S4N431N431X4314S1+A441计量(兼用 测量)+B441计量(兼用 测量)+C441计量(兼用测 量)4S24S34S4N441N4414412 变比试验二次绕 组编号A相B相C相标准值标准值标准值
5、0. 5A1A5A0. 5A1A5A0. 5A1A5A实测值实测值实测值1S1-1S2200/5200/5200/5200/5200/5200/5200/5200/5200/51S1-1S3400/5400/5400/5400/5400/5400/5400/5400/5400/51S1-1S4600/5600/5600/5600/5600/5600/5600/5600/5600/52S1-2S2200/5200/5200/5200/5200/5200/5200/5200/5200/52S1-2S3400/5400/5400/5400/5400/5400/5400/5400/5400/52S1-
6、2S4600/5600/5600/5600/5600/5600/5600/5600/5600/53S1-3S2200/5200/5200/5200/5200/5200/5200/5200/5200/53S1-3S3400/5400/5400/5400/5400/5400/5400/5400/5400/53S1-3S4600/5600/5600/5600/5600/5600/5600/5600/5600/54S1-4S2200/5200/5200/5200/5200/5200/5200/5200/5200/54S1-4S3400/5400/5400/5400/5400/5400/5400/540
7、0/5400/54S1-4S4600/5600/5600/5600/5600/5600/5600/5600/5600/53伏安特性试验相 别绕组0. 1A0. 2A0. 4A0. 6A0. 8A1A2A3A4A5AA相1S1-1S269.299.9116.8122. 5125.8128.0130.4132.7134.6136.01S1-1S3200.2228.9244.2250.8254.4257.9267.4271. 1272.9274.41S1-1S4339.9366.7383.6392. 3394. 1396.0410. 3413.8415.9417. 72S1-2S279.0105.3
8、119.5124. 7127.8129.8131.4133.4135.0136. 12S1-2S3208.8233.9250. 1254. 5258.2260. 5267.3270. 7273. 1274. 52S1-2S4338.8366.6384.6393. 1394.8396.6409.3412.4414.3416. 13S1-3S237. 743.345.947.448.048. 349.449.850.250.43S1-3S386.991.895.396.898.098. 399.8100. 1100.7101. 13S1-3S4134.3138.5142.5144. 3145.81
9、46.5148. 7149. 1149.4150.24S1-4S210.210.310.410.410. 710. 71111. 111.411. 54S1-4S320.220.620. 720.921. 121.121.321.421.822. 14S1-4S430.831.331.631. 732.132. 132.332.432.833. 1B相1S1-1S270.2100.9118.8125.6128129. 5132.3133.6137139. 11S1-1S3201.2229.9247.2251. 7255.9261. 5270.3272.6275.8279.01S1-1S4349
10、.3376.9389.6392. 1394.6397409.8412.6414.7416.52S1-2S280.0106.2120. 1125.6128. 7131.9133. 7134.6136.3136. 12S1-2S3210. 7233.9250. 1254. 5258.2260. 5267. 3270.7273. 1274. 52S1-2S4350.3376.8389. 5395.0396. 7398.6413. 1416.2418. 1419.03S1-3S238. 745.346. 148. 148.648.849.649.650.350.63S1-3S387.992. 595.
11、 797. 598.298.499.9100.3100.8101. 33S1-3S4134.8138.8142.7144.8146.2146. 7148.9149.2150150.74S1-4S210.410.510.610.610.810.911. 111.211.511.64S1-4S320.320.721.021.021.221.221.521.521.822.24S1-4S430.030.430.630.831.031. 131.431.532.032. 3C相1S1-1S265.296.9115.8123.6125.0126.5127.3132.6136.0138. 11S1-1S3
12、198.9225.8243.4250.4253. 7259. 5266.3268.6274.8276.01S1-1S4336.3364.7379.3387.3391.9395.5410.0413.7416.0418.02S1-2S277.0105.0118. 1123.6125. 7128.9131. 7133.6135.3136. 12S1-2S3203.7231.8247. 1253. 5255.2257.5267.3266.7269. 1271. 52S1-2S4342.2374.0384.8391.9395. 6398.4411.9414.9416.9418.03S1-3S237. 7
13、43.345. 146. 146.646.847.647.648.348.63S1-3S385.991.593. 796.596.297.498.999.399.8100.43S1-3S4133.0138.3140.9142.6143. 7143. 7144.3146.0147. 1147.84S1-4S210.210.310.410.410.610. 710.911.011.211. 34S1-4S320.220.520.820.821.021.021. 321.321.621.94S1-4S429.830. 530.830.931.231.231. 531. 732. 232.44升流试验(一次试验班)用途回路编号一次电流二次电流实测变比保护A4111201A600/5B4111A600/5C4111A600/5保护(备用)A4211A600/5B4211A600/5C4211A600/5测量(备用)A4311A600/5B4311A600/5C4311A600/5计量(兼用测量)A4411A600/5B4411A600/5C4411A600/55结论XXX开关CT现场调试完毕。经上述检验,各项技术指标符合规程及厂家的标准和要求,CT极性(减极性)及变比正确,伏安特性试验合格,二次回路完好,可以投入运行。